Delta Electronics VFD-M manual Summary of Parameter Settings, Explanation, Factory

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 37
Image 37

Chapter 4 Parameters4.1 Summary of Parameter Settings

4.1 Summary of Parameter Settings

: The parameter can be set during operation.

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

 

 

 

 

 

 

 

 

Pr.00

Source of Frequency

00: Master frequency determined by digital

00

 

 

 

 

 

Command

keypad (LC-M02E)

 

 

 

 

 

 

 

01: Master frequency determined by 0 to

 

 

 

 

 

 

 

+10 V input on AVI terminal with jumpers

 

 

 

 

 

 

 

02: Master frequency determined by 4 to

 

 

 

 

 

 

 

20mA input on ACI terminal with jumpers

 

 

 

 

 

 

 

03: Master frequency determined by RS-485

 

 

 

 

 

 

 

Communication port

 

 

 

 

 

 

 

04: Master frequency determined by

 

 

 

 

 

 

 

potentiometer on digital keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.01

Source of Operation

00: Operation determined by digital keypad

00

 

 

 

 

 

command

01: Operation determined by external control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals, keypad STOP is effective

 

 

 

 

 

 

 

02: Operation determined by external control

 

 

 

 

 

 

 

terminals, keypad STOP is ineffective

 

 

 

 

 

 

 

03: Operation determined by RS-485

 

 

 

 

 

 

 

communication port, keypad STOP is

 

 

 

 

 

 

 

effective

 

 

 

 

 

 

 

04: Operation determined by RS-485

 

 

 

 

 

 

 

communication port, keypad STOP is

 

 

 

 

 

 

 

ineffective

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.02

Stop Method

00: Ramp stop

00

 

 

 

 

 

 

01: Coast Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.03

Maximum Output

50.00 to 400.0 Hz

60.00

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.04

Maximum Voltage

10.00 to 400.0Hz

60.00

 

 

 

 

 

Frequency (Base

 

 

 

 

 

 

 

Frequency)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115V/230V: 0.1 to 255.0V

220.0

 

 

 

 

Pr.05

Maximum Output

 

 

 

 

 

 

460V: 0.1 to 510.0V

440.0

 

 

 

 

Voltage (Vmax)

 

 

 

 

 

 

 

 

 

 

 

 

 

575V: 0.1 to 637.0V

575.0

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06

Mid-point Frequency

0.10 to 400.0Hz

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115V/230V: 0.1 to 255.0V

10.0

 

 

 

 

Pr.07

Mid-point Voltage

 

 

 

 

 

 

460V: 0.1 to 510.0V

20.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575V: 0.1 to 637.0V

26.1

 

 

 

 

 

 

 

 

 

 

4-2

Revision May 2008, ME14, SW V3.04