Delta Electronics VFD-M manual +10V DC or 4 to 20mA DC. Refer to the following examples

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 79
Image 79
+10V DC or 4 to 20mA DC). Refer to the following examples.

Chapter 4 ParametersManual background

Pr.48 to Pr.51 are used when the source of frequency command is the analog signal (0 to

+10V DC or 4 to 20mA DC). Refer to the following examples.

Example 1:

Set Pr.00=1 to command frequency with the potentiometer on keypad or Pr.00=2 (4 to 20mA current signal) potentiometer/current signal of external terminal.

Max.

Output Pr.03

Freq.

60Hz

 

Factory Settings

 

30

 

 

 

 

 

 

 

 

 

 

 

 

Pr.03=60Hz--Max. output Freq.

 

 

 

 

Pr.48=0%--bias adjustment

 

 

 

 

 

Pr.49=0 -- bias polarity

 

 

 

 

 

Pr.50=100% -- pot. freq. gain

0

 

60

 

 

Pr.51=0 -- REV disable in

Hz

 

 

0V

10V

0Hz

 

negative bias

 

 

Potentiometer Scale

0V

5V

10V

4mA

12mA

20mA

 

 

 

Example 2:

A Bias Adjustment (16.7% of 60Hz) determines the Output Frequency to be 10 Hz with the potentiometer set at 0V as shown. Notice that the entire V/F is transposed accordingly. An analog input voltage 0-8.33V (or current 4-13.33mA) would set frequency as 0-60Hz.Once the Maximum Output Frequency is reached any further increase on the potentiometer will not increase output frequency (If you want to use the range of 60Hz, please refer to the example 3).

Max.

 

Output Pr.03

 

Freq.

 

60Hz

 

Bias 10Hz

 

Adjustment

 

0Hz 0V

5V

4mA

12mA

Factory Settings

Pr.03=60Hz--Max. output Freq. Pr.48=16.7%-- bias adjustment Pr.49=0 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.51=0 -- REV motion disable in negative bias

10V

20mA

 

40

 

 

60

It is

10

 

Hz

60Hz

0V

10V

in this

range.

Potentiometer Scale

4-44

Revision May 2008, ME14, SW V3.04

Page 79
Image 79
Delta Electronics VFD-M manual +10V DC or 4 to 20mA DC. Refer to the following examples