Delta Electronics VFD-M manual B.4 AC Reactor B.4.1 AC Input Reactor Recommended Value

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 152
Image 152
B.4 AC Reactor

Appendix B AccessoriesB.4.2 AC Output Reactor Recommended Value

B.4 AC Reactor

B.4.1 AC Input Reactor Recommended Value

230V, 50/60Hz, single-phase

kW

HP

Fundamental

Max. continuous Amps

Amps

 

 

 

 

 

 

 

0.2

0.25

4

6

 

 

 

 

0.4

0.5

5

7.5

 

 

 

 

0.75

1

8

12

 

 

 

 

1.5

2

12

18

2.2

3

18

27

 

 

 

 

460V, 50/60Hz, 3-phase

Inductance (mh) 3~5% Impedance

6.5

3

1.5

1.25

0.8

kW

HP

Fundamental

Max. continuous

Inductance (mh)

 

Amps

Amps

3% Impedance

5% Impedance

 

 

 

 

 

 

 

 

 

0.75

1

4

6

9

12

 

 

 

 

 

 

 

 

1.5

2

4

6

6.5

9

 

 

 

 

 

 

 

 

2.2

3

8

12

5

7.5

 

 

 

 

 

 

 

 

3.7

5

8

12

3

5

 

 

 

 

 

 

 

 

5.5

7.5

12

18

2.5

4.2

 

 

 

 

 

 

 

 

7.5

10

18

27

1.5

2.5

 

 

 

 

 

 

 

 

11

15

25

37.5

1.2

2

 

B.4.2 AC Output Reactor Recommended Value

115V/230V, 50/60Hz, 3-phase

 

 

 

 

kW

HP

Fundamental

Max. continuous

Inductance (mh)

 

Amps

Amps

3% Impedance

5% Impedance

 

 

 

 

0.2

0.25

4

6

9

12

 

 

 

 

 

 

 

 

0.4

0.5

4

6

6.5

9

 

 

 

 

 

 

 

 

0.75

1

8

12

3

5

 

 

 

 

 

 

 

 

1.5

2

8

12

1.5

3

 

 

 

 

 

 

 

 

2.2

3

12

18

1.25

2.5

 

 

 

 

 

 

 

 

3.7

5

18

27

0.8

1.5

 

 

 

 

 

 

 

 

5.5

7.5

25

37.5

0.5

1.2

 

 

 

 

 

 

 

Revision May 2008, ME14, SW V3.04