Chapter 4 Parameters

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

 

 

Pr.30

DC Braking during

0.0 to 25.0 sec

0.0

 

 

 

 

Stopping

 

 

 

 

 

 

 

 

 

 

 

Pr.31

Start-point for DC

0.00 to 60.00 Hz

0.00

 

 

 

 

Braking

 

 

 

 

 

 

 

 

 

 

 

 

 

00: Stop operation after momentary power

 

 

 

 

 

 

 

loss

 

 

 

 

 

 

Momentary Power

01: Continues after momentary power loss,

 

 

 

 

 

 

speed search starts with Master

 

 

 

 

 

Pr.32

Loss Operation

00

 

 

 

 

Frequency

 

 

 

 

 

Selection

 

 

 

 

 

 

02: Continues after momentary power loss,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed search starts with Minimum output

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.33

Maximum Allowable

0.3 to 5.0 sec

2.0

 

 

 

 

Power Loss Time

 

 

 

 

 

 

 

 

 

 

 

Pr.34

Base-Block Time for

0.3 to 5.0 sec

0.5

 

 

 

 

Speed Search

 

 

 

 

 

 

 

 

 

 

 

Pr.35

Maximum Current

30 to 200 %

150

 

 

 

 

Level for Speed

 

 

 

 

 

 

 

 

 

 

Search

 

 

 

 

 

 

Pr.36

Upper Bound of

0.10 Hz to 400.0 Hz

400.0

 

 

 

 

Output Frequency

 

 

 

 

 

 

 

 

 

 

 

Pr.37

Lower Bound of

0.00 Hz to 400.0 Hz

0.00

 

 

 

 

Output Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

00: M0: FWD/STOP, M1: REV/STOP

 

 

 

 

 

Pr.38

Multi-function Input

01: M0: RUN/STOP, M1: REV/FWD

00

 

 

 

 

Terminal (M0,M1)

02: M0, M1, M2: 3-wire operation control

 

 

 

 

 

 

 

 

 

 

 

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.39

Multi-function Input

00: No Function

05

 

 

 

 

Terminal (M2)

01: Output OFF (N.O.) (enabled when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi-function Input

running)

 

 

 

 

 

Pr.40

02: Output OFF (N.C.) (enabled when

06

 

 

 

 

Terminal (M3)

 

 

 

 

 

running)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03: External Fault (normally open) N.O.

 

 

 

 

 

 

Multi-function Input

 

 

 

 

 

Pr.41

04: External Fault (normally close) N.C

07

 

 

 

 

Terminal (M4)

 

 

 

 

 

05: RESET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06: Multi-Step Speed Command 1

 

 

 

 

 

 

 

07: Multi-Step Speed Command 2

 

 

 

 

 

 

Multi-function Input

08: Multi-Step Speed Command 3

 

 

 

 

 

Pr.42

09: Jog Operation

08

 

 

 

 

Terminal (M5)

 

 

 

 

 

10: Accel/Decel Speed Inhibit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11: First or Second Accel/Decel Time

 

 

 

 

 

 

 

12: Base-block (B.B.) (N.O)

 

 

 

 

 

 

 

 

 

 

 