Delta Electronics VFD-M manual Parameter Settings for Applications

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 49
Image 49

Chapter 4 Parameters4.2 Parameter Settings for Applications

4.2 Parameter Settings for Applications

Speed Search

Applications

Purpose

Functions

Related

Parameters

 

 

 

Windmill, winding

Restart free-

Before the free-running motor is

Pr.32~Pr.35

machine, fan and all

running motor

completely stopped, it can be restarted

 

inertia loads

 

without detection of motor speed. The

 

 

 

AC motor drive will auto search motor

 

 

 

speed and will accelerate when its

 

 

 

speed is the same as the motor speed.

 

DC Braking before Running

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

When e.g. windmills,

Keep the free-

If the running direction of the free-

Pr.28

fans and pumps rotate

running motor at

running motor is not steady, please

Pr.29

freely by wind or flow

standstill.

execute DC braking before start-up.

 

without applying power

 

 

 

Energy Saving

 

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

Punching machines

Energy saving and

Energy saving when the AC motor

Pr.95

fans, pumps and

less vibrations

drive runs at constant speed, yet full

 

precision machinery

 

power acceleration and deceleration

 

 

 

For precision machinery it also helps

 

 

 

to lower vibrations.

 

Multi-step Operation

 

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

Cyclic operation by

To control 7-step speeds and duration

Pr.17~Pr.23

Conveying machinery

Pr.78~Pr.79

multi-step speeds.

by simple contact signals.

 

Pr.81~Pr.87

 

 

 

 

 

 

 

4-14

Revision May 2008, ME14, SW V3.04