Delta Electronics VFD-M manual Parameter, Explanation, Settings, Factory

Models: VFD-M

1 173
Download 173 pages 14.33 Kb
Page 43
Image 43

Chapter 4 ParametersManual background

 

 

Parameter

Explanation

Settings

Factory

Customer

 

 

 

Setting

 

 

 

 

PWM Carrier

115V/230V/460V series: 01 to 15

15

 

 

 

 

Pr.71

(The factory setting of VFD075M43A is 10)

 

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

575V series: 01 to 10

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.72

Auto Restart Attempts

00 to 10

00

 

 

 

 

 

after Fault

 

 

 

 

 

 

 

 

00: No fault occurred

 

 

 

 

 

 

 

01: Over-current (oc)

 

 

 

 

 

Pr.73

Present Fault Record

02: Over-voltage (ov)

00

 

 

 

 

03: Overheat (oH)

 

 

 

 

 

 

 

 

 

 

 

 

 

04: Overload (oL)

 

 

 

 

 

 

 

05: Overload 1 (oL1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06: External Fault (EF)

 

 

 

 

 

 

 

07: CPU failure 1 (CF1)

 

 

 

 

 

 

 

08: CPU failure 3 (CF3)

 

 

 

 

 

Pr.74

Second Most Recent

09: Hardware Protection Failure (HPF)

00

 

 

 

 

Fault Record

10: Over-current during acceleration (oca)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11: Over-current during deceleration (ocd)

 

 

 

 

 

 

 

12: Over-current during steady state

 

 

 

 

 

 

 

operation (ocn)

 

 

 

 

 

 

 

13: Ground fault or fuse failure(GFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14: Low Voltage (not record)

 

 

 

 

 

 

 

15: 3 Phase Input Power Loss

 

 

 

 

 

 

Third Most Recent

16: EPROM failure (CF2)

 

 

 

 

 

Pr.75

17: External interrupt allowance(bb)

00

 

 

 

 

Fault Record

 

 

 

 

 

18: Overload (oL2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19: Auto Adjustable accel/decel failure

 

 

 

 

 

 

 

(CFA)

 

 

 

 

 

 

 

20: CPU self detection failure (codE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00: All parameters can be set/read

 

 

 

 

 

 

 

01: All parameters are read-only

 

 

 

 

 

Pr.76

Parameter Lock and

02-08: Reserved

00

 

 

 

 

09: Resets all parameters to 50Hz factory

 

 

 

 

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

defaults

 

 

 

 

 

 

 

10: Resets all parameters to 60Hz factory

 

 

 

 

 

 

 

defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.77

Time for Auto Reset

0.1 to 6000.0 sec

60.0

 

 

 

 

the Restart Times in

 

 

 

 

 

 

 

 

 

 

Abnormality

 

 

 

 

4-8

Revision May 2008, ME14, SW V3.04

Page 43
Image 43