Chapter 4 Parameters
Frequency |
|
|
Max. |
|
|
Output |
|
|
Freq. |
| Actual Acceleration/Deceleration Time= |
|
| |
|
| Acceleration/Deceleration Time x(Master |
|
| Max. Output Freq. |
Pr.10 | Pr.11 | Time |
| ||
or | or |
|
|
| Pr. 12 | Pr. 13 |
|
| Acceleration Time | Deceleration Time |
|
|
| |
| Pr.14 | Acceleration | |
|
| Settings 00 to 07 | Factory Setting: 00 |
|
|
|
|
This parameter is used whenever the motor load needs to be accelerated or decelerated smoothly. The desired accel/decel effect is selectable from 0 to 7, in which the larger the number, the greater the effect achieved. If the default value of Pr.111 Deceleration S Curve is unchanged (“0”), then Pr.14 sets both acceleration and deceleration
Freq.
|
| Acceleration/Deceleration characteristics |
| |
|
| (1), (2) | Disabling S curve |
|
|
| (3), (4) | Enabling S curve |
|
|
|
|
|
|
| Pr.15 | Jog Accel / Decel Time |
| Unit: 0.1 or 0.01 sec |
|
| Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec | Factory Setting: 1.0 sec | |
|
|
|
|
|
This parameter sets the acceleration or deceleration time for Jog operation.
Pr.16 | Jog Frequency | Unit: 0.1 | Hz |
| Settings 0.00 to 400.0 Hz | Factory Setting: 6.00 | Hz |
Revision May 2008, ME14, SW V3.04 |