Chapter 4 Parameters

 

Settings

Function

Description

21

RESET Command (N.C)

 

 

 

 

 

22

Control source: External

Enter values 22, 23, or 24 to set the control source to be the

Terminal

external terminals, keypad or communication respectively.

 

 

 

 

 

This setting is used to create functions for manual/auto, and

23

Control source: Keypad

remote/near-end control. When these three functions are

 

 

 

24

Control source:

used at the same time, the priority is 22-I/O > 23-Keypad >

Communication

24-Communication.

 

 

 

 

 

 

 

 

Parameter Lock (Write

This function will disable the write function and all the content

 

 

of read are 0. The application is for customer having a key to

25

disable, Read is always

control the operator to modify parameters or modify the

 

 

0)

 

 

parameter by improper use.

 

 

 

 

 

 

26

PID Disable (N.O.)

This function pause the PID control. It is commonly used for

 

 

 

manual operation or function testing, and to recover the PID

27

PID Disable (N.C.)

function when the system is normal.

 

 

 

 

 

 

28

Second Source for

This function is used with Pr. 142 to select a different

 

 

Frequency Command

frequency source for control.

 

 

 

29

Forward (contact is

This function has top priority to set the direction for running (If

 

 

open) / Reverse (contact

“Pr. 24 inhibit REV function” is not set). No mater what the

 

 

is close)

present direction of run is, the contact N.O. is forward and the

 

 

 

contact N.C. is reverse, once this function is set.

 

 

 

The requirement for setting direction is Pr. 24 > setting 29 of

 

 

 

Pr. 39-Pr. 42 > Pr. 38.

 

 

 

30

One-Shot PLC Run

 

 

 

 

31

Index Input Signal

This function is used with parameters 149 to 151. The position

 

 

 

where AC drive stops will be regarded as the zero position

 

 

 

and it will move to the angle that Pr. 150 sets.

 

 

 

32

Virtual Timer Input

This function is for counting at the speed of the output

 

 

 

frequency.

 

 

 

 

Note: The settings 00~32 in Pr. 39 to Pr.42 can be used to set multi-function terminals (M2-M5) but the settings cannot be used repeatedly at the same time (besides settings 20).

Revision May 2008, ME14, SW V3.04