3–37

 

SJ300 Inverter

 

 

Miscellaneous

The miscellaneous settings include scaling factors, initialization modes, and others. This

Settings

section covers some of the most important settings you may need to configure.

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

Name

Description

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B034

Run/power-on warning

Range is 0 to 65,530 hours

✘ ✔

0.

0.

 

0.

hrs.

>b034 TIME

 

 

time

 

 

 

 

 

 

 

WARN

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B035

Rotational direction

Three option codes:

✘ ✘

00

00

 

00

>b035 LIMIT

 

 

restriction

00 Enable for both dir.

 

 

 

 

 

 

F/R

FREE

 

 

 

 

 

 

 

 

 

 

 

01 Enable for forward only

 

 

 

 

 

 

 

 

 

 

02 Enable for reverse only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B036

Reduced voltage start

Seven option codes:

✘ ✔

06

06

 

06

>b036 RVS

 

 

selection

00 Short

 

 

 

 

 

 

ADJUST

06

 

 

 

 

 

 

 

 

 

 

 

01, 02, 03, 04, 05 (middle)

 

 

 

 

 

 

 

 

 

 

06 Long

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function Code Display Restriction – The inverter has the (optional) capability to suppress the

 

display and editing of certain parameters. Use B037 to select the display options. The purpose

 

of this feature is to hide particular secondary parameters that become unused or not applicable

 

based on more fundamental parameter settings. For example, setting A001 = 01 configures the

 

inverter to get its frequency command from the front keypad potentiometer. In this case, the

 

inverter will not use the analog inputs nor their adjustment parameters for an external frequency

 

command.

 

 

 

 

 

 

 

 

Parameters

Drive Configuring

 

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

Name

Description

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B037

Function code display

Three option codes:

✘ ✔

00

00

 

00

>b037 DISP

 

restriction

00 Display all

 

 

 

 

 

 

Mode

ALL

 

 

 

 

 

 

 

 

 

 

 

01 Display only utilized

 

 

 

 

 

 

 

 

 

 

functions (see table

 

 

 

 

 

 

 

 

 

 

below)

 

 

 

 

 

 

 

 

 

 

02 Display user-selected

 

 

 

 

 

 

 

 

 

 

functions only (con-

 

 

 

 

 

 

 

 

 

 

figure with U01 to U12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For example, you can set B037=01 to have the inverter suppress the displaying of all analog input parameters when A001=01, as shown in the first row of the following table.

 

Function

Data

Resulting Non-displayed

Notes

 

 

Code

Functions (when B37 = 01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A001

01

A005, A006, A011 – A016,

[O], [OI], [O2] terminal

 

 

 

 

A101 – A114, C081 – C083,

functions

 

 

 

 

C121 – C123

 

 

 

 

 

 

 

 

 

A002

01, 03, 04,

B087

Stop key function

 

 

 

05

 

 

 

 

 

 

 

 

 

 

A019

00

A028 – A035

Multi-speed function

 

 

 

 

 

 

 

 

C001 – C008

02, 03, 04,

 

 

 

 

 

05