UL® Cautions, Warnings, and Instructions

Wiring Warnings for Electrical Practices and Wire Sizes

The Cautions, Warnings, and instructions in this section summarize the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories® guidelines.

WARNING: “Use 60/75°C Cu wire only” or equivalent.

WARNING: “Open Type Equipment.” For models SJ300–750H to SJ300–1500H.

Terminal Tightening Torque and Wire Size

WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 240 V maximum.” For models with suffix L.

WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H.

The wire size range and tightening torque for field wiring terminals are presented in the table below.

Input

Motor

200V

 

Torque

Output

Wire Size Range (AWG)

 

 

Voltage

 

 

Inverter Model

 

 

HP

kW

 

ft-lbs

(N-m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

0.4

SJ300-004LFU

20

1.1

1.5

 

 

 

 

 

 

 

 

1

0.75

SJ300-007LFU

18

1.1

1.5

 

 

 

 

 

 

 

 

2

1.5

SJ300-015LFU

14

1.1

1.5

 

 

 

 

 

 

 

 

3

2.2

SJ300-022LFU

14

1.1

1.5

 

 

 

 

 

 

 

 

5

3.7

SJ300-037LFU

10

1.1

1.5

 

 

 

 

 

 

 

 

7.5

5.5

SJ300-055LFU

8

1.8

2.5

 

 

 

 

 

 

 

 

10

7.5

SJ300-075LFU

6

1.8

2.5

200V

 

 

 

 

 

 

15

11

SJ300-110LFU

4

3.6

4.9

 

 

 

 

 

 

 

 

20

15

SJ300-150LFU

2

3.6

4.9

 

 

 

 

 

 

 

 

25

18.5

SJ300-185LFU

1

3.6

4.9

 

 

 

 

 

 

 

 

30

22

SJ300-220LFU

1/0 AWG

6.5

8.8

 

 

 

 

 

 

 

 

40

30

SJ300-300LFU

1/0 1/0 AWG

6.5

8.8

 

 

 

 

 

 

 

 

50

37

SJ300-370LFU

1/0 1/0 AWG

6.5

8.8

 

 

 

 

 

 

 

 

60

45

SJ300-450LFU

1/0 1/0 AWG

10.1

13.7

 

 

 

 

 

 

 

 

75

55

SJ300-550LFU

2/0 2/0 AWG

10.1

13.7