UL® Cautions, Warnings, and Instructions
The Cautions, Warnings, and instructions in this section summarize the procedures necessary to ensure an inverter installation complies with Underwriters Laboratories® guidelines.
WARNING: “Use 60/75°C Cu wire only” or equivalent.
WARNING: “Open Type Equipment.” For models
Terminal Tightening Torque and Wire Size
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 240 V maximum.” For models with suffix L.
WARNING: “Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 480 V maximum.” For models with suffix H.
The wire size range and tightening torque for field wiring terminals are presented in the table below.
Input | Motor | 200V |
| Torque | |||
Output | Wire Size Range (AWG) | ||||||
|
| ||||||
Voltage |
|
| Inverter Model |
|
| ||
HP | kW |
| |||||
|
|
| |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
| 1/2 | 0.4 | 20 | 1.1 | 1.5 | ||
|
|
|
|
|
|
| |
| 1 | 0.75 | 18 | 1.1 | 1.5 | ||
|
|
|
|
|
|
| |
| 2 | 1.5 | 14 | 1.1 | 1.5 | ||
|
|
|
|
|
|
| |
| 3 | 2.2 | 14 | 1.1 | 1.5 | ||
|
|
|
|
|
|
| |
| 5 | 3.7 | 10 | 1.1 | 1.5 | ||
|
|
|
|
|
|
| |
| 7.5 | 5.5 | 8 | 1.8 | 2.5 | ||
|
|
|
|
|
|
| |
| 10 | 7.5 | 6 | 1.8 | 2.5 | ||
200V |
|
|
|
|
|
| |
15 | 11 | 4 | 3.6 | 4.9 | |||
|
|
|
|
|
|
| |
| 20 | 15 | 2 | 3.6 | 4.9 | ||
|
|
|
|
|
|
| |
| 25 | 18.5 | 1 | 3.6 | 4.9 | ||
|
|
|
|
|
|
| |
| 30 | 22 | 1/0 AWG | 6.5 | 8.8 | ||
|
|
|
|
|
|
| |
| 40 | 30 | 1/0 1/0 AWG | 6.5 | 8.8 | ||
|
|
|
|
|
|
| |
| 50 | 37 | 1/0 1/0 AWG | 6.5 | 8.8 | ||
|
|
|
|
|
|
| |
| 60 | 45 | 1/0 1/0 AWG | 10.1 | 13.7 | ||
|
|
|
|
|
|
| |
| 75 | 55 | 2/0 2/0 AWG | 10.1 | 13.7 | ||
|
|
|
|
|
|
|