2–26

Using the Front Panel Keypad

Inverter Mounting

and Installation

 

 

Selecting Functions and Editing Parameters

In order to run the motor for the powerup test, this section will show how to:

select the inverter’s maximum output frequency to the motor

select the keypad potentiometer as the source of motor speed command

select the keypad as the source of the RUN command

set the number of poles for the motor

enable the RUN command

The following series of programming tables are designed for successive use. Each table uses the previous table’s final state as the starting point. Therefore, start with the first and continue programming until the last one. If you get lost or concerned that some of the other parameters settings may be incorrect, refer to “Restoring Factory Default Settings” on page 6–9.

CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage.

Setting the Motor Base Frequency -The motor is designed to operate at a specific AC frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the motor specifications. Then follow the steps in the table below to verify the setting or correct for your motor. DO NOT set it for greater than 50/60 Hz unless the motor manufacturer specifically approves operation at the higher frequency.

 

 

ActionDisplayFunc./Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

d 0 0 1

Monitor functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

or

2

keys until ->

A – – –

“A” Group selected

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

A 0 0 1

First “A” parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

key twice.

A 0 0 3

Base frequency setting

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

6 0

Default value for base frequency

 

US = 60 Hz, Europe = 50 Hz

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

5 0

 

 

 

 

 

 

 

 

Press the

1

or

2

key as needed.

6 0

Set to your motor specs (your

display may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Press the

STR

key.

 

A 0 0 3

Stores parameter, returns to “A”

 

Group list

 

 

 

 

 

 

 

 

 

 

 

 

TIP: If you need to scroll through a function or parameter list, press and hold the 1 or 2 key to auto-increment through the list.