4–31

SJ300 Inverter

Internal SpeedLoop Gain

Settings

When sensorless vector control, 0Hz sensorless vector control, or vector control with sensor is selected for the control method, the Control Gain Switching function selects between two sets of gains in the internal speed loop. These gains are used in proportional and integral compensa- tion. Use option code 26 to assign the [CAS] function to an intelligent input terminal. Use option code 43 to select between P and PI control.

Opt.

 

Symbol

Function Name

 

Input

 

 

 

 

 

Description

 

 

 

 

 

 

 

Code

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

CAS

Control Gain

 

ON

Gains in parameters H070, H071, and

 

 

 

 

Switching

 

 

H072 are selected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Gains in parameters H050, H051, H052;

 

 

 

 

 

 

 

or, H250, H251, H252 (2nd motor) are

 

 

 

 

 

 

 

selected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43

 

 

PPI

P / PI Control

 

ON

Selects Proportional control (P)

 

 

 

 

 

 

 

 

Switching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Selects Proportional-Integral control (PI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

 

C001, C002, C003, C004,

Example: (Requires input configuration—

inputs:

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

 

A044 / A244 / A344 =

 

see page 4–12.)

 

 

 

CAS

 

 

 

 

 

03 (SLV), or

 

 

 

 

 

 

 

 

 

 

 

PPI

 

 

 

 

 

 

 

settings:

 

 

04 (0 Hz domain), or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

FW

8

 

CM1

5

 

3

 

1

 

 

 

 

 

05 (V2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When Control Gain Switching is not selected for an intelligent input terminal, the default

gains in effect correspond to the OFF state of

See I/O

[CAS].

specs on

 

 

page 4–9.

The table below lists the functions and parameter settings related to internal speed loop gains.

Function Code

Parameter

Setting Range

Description

 

 

 

 

 

 

 

 

 

 

03

SLV (does not use A344)

 

 

 

 

A044 / A244 /

Control method

04

0-Hz Domain SLV (does not

 

use A344)

A344

selection

 

 

 

 

 

05

V2 (does not use A244 or

 

 

 

A344)

 

 

 

 

C001 - C008

Intelligent input

43

PPI : P/I switching

 

selection

 

 

 

 

 

 

H005 / H205

Speed response

0.001 to 65.53

No dimension

 

 

 

 

H050 / H250

PI proportional gain

0.0 to 999.9/1000

% gain

 

 

 

 

H051 / H251

PI integral gain

0.0 to 999.9/1000

% gain

 

 

 

 

H052 / H252

P proportional gain

0.01 to 10.00

No dimension

 

 

 

 

H070

PI proportional gain

0.0 to 999.9/1000

% gain

 

for switching

 

 

 

 

 

 

H071

PI integral gain for

0.0 to 999.9/1000

% gain

 

switching

 

 

 

 

 

 

H072

P proportional gain

0.0 to 10.0

No dimension

 

for switching

 

 

 

 

 

 

Operations Monitoring and