SJ300 Inverter

Remote ControlUp and Down

Functions

The [UP] [DWN] terminal functions can adjust the output frequency for remote control while the motor is running. The acceleration time and deceleration time used with this function is the same as for normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate as follows:

Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from the current value. When it is turned OFF, the output frequency maintains its current value.

Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates from the current value. When it is turned OFF, the output frequency maintains its current value.

In the graph below, the [UP] and [DWN] terminals activate while the Run command remains ON. The output frequency responds to the [UP] and [DWN] commands.

Output

frequency

[UP]

[DWN]

[FW, RV]

t

It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency.

Opt.

 

Symbol

Function Name

 

Input

 

 

 

 

 

 

Description

 

 

 

Code

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

 

UP

Remote Control

 

ON

Accelerates (increases output frequency)

 

 

 

UP Function

 

 

motor from current frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

DWN

Remote Control

 

ON

Decelerates (decreases output frequency)

 

 

 

DOWN Function

 

 

motor from current frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

UDC

Remote Control

 

ON

Clears the Up/down frequency memory

 

 

 

Data Clear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No effect on Up/down memory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example: (Requires input configuration—

 

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

A001 = 02

 

 

see page 4–12.)

 

 

 

 

 

 

 

 

 

 

settings:

 

C101 = 01 (enables memory)

 

 

 

 

 

 

 

 

 

 

UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

UDC DWN

 

 

 

 

 

 

This feature is available only when the

 

 

 

TH

FW

8

CM1

5

3

1

 

frequency command source is programmed

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

for operator control. Confirm A001 is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This function is not available when [JG] is in

use.

The range of output frequency is 0 Hz to the value in A004 (maximum frequency setting).

The Remote Control Up/Down function

varies the inverter speed by directly writing to See I/O specs on page 4–9.the F001 output frequency setting.