The [UP] [DWN] terminal functions can adjust the output frequency for remote control while the motor is running. The acceleration time and deceleration time used with this function is the same as for normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate as follows:
•Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from the current value. When it is turned OFF, the output frequency maintains its current value.
•Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates from the current value. When it is turned OFF, the output frequency maintains its current value.
In the graph below, the [UP] and [DWN] terminals activate while the Run command remains ON. The output frequency responds to the [UP] and [DWN] commands.
Output
frequency
[UP]
[DWN]
[FW, RV]
t
It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency.
Opt. |
| Symbol | Function Name |
| Input |
|
|
|
|
|
| Description |
|
|
| ||||||||
Code |
|
| State |
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
27 |
| UP | Remote Control |
| ON | Accelerates (increases output frequency) | |||||||||||||||||
|
|
| UP Function |
|
| motor from current frequency |
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | Output to motor operates normally | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
28 |
| DWN | Remote Control |
| ON | Decelerates (decreases output frequency) | |||||||||||||||||
|
|
| DOWN Function |
|
| motor from current frequency |
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | Output to motor operates normally | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
29 |
| UDC | Remote Control |
| ON | Clears the Up/down frequency memory | |||||||||||||||||
|
|
| Data Clear |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | No effect on Up/down memory | ||||||||||||||||||
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C001, C002, C003, C004, | Example: (Requires input configuration— | |||||||||||||||||||||
|
|
| C005, C006, C007, C008 | see page | |||||||||||||||||||
|
|
|
|
|
| for | |||||||||||||||||
Required | A001 = 02 |
| |||||||||||||||||||||
| see page |
|
|
|
|
|
|
|
|
|
| ||||||||||||
settings: |
| C101 = 01 (enables memory) |
|
|
|
|
|
|
|
|
|
| UP |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Notes: |
|
|
|
|
|
|
|
|
| UDC DWN |
|
|
|
|
|
| |||||||
• This feature is available only when the |
|
|
| TH | FW | 8 | CM1 | 5 | 3 | 1 |
| ||||||||||||
frequency command source is programmed |
| P24 | PLC | CM1 |
| 7 | 6 |
| 4 |
| 2 |
|
| ||||||||||
for operator control. Confirm A001 is set to |
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
02. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•This function is not available when [JG] is in
use.
• The range of output frequency is 0 Hz to the value in A004 (maximum frequency setting).
• The Remote Control Up/Down function