2–15

SJ300 Inverter

Determining wire and fuse sizes, continued...

Motor

 

 

 

 

Wiring *1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

400V

 

Power Lines *3

 

Chassis Ground

Brake Res.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

Fuse

Breaker

 

 

 

 

 

 

 

HP

kW

Models

AWG

mm2

(UL-

AWG,

AWG,

mm2

AWG

mm2

 

 

 

rated,

( GFI

rec.

UL

 

 

 

 

 

 

 

class J,

type) *2

 

 

 

 

MountingInverter Installationand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

0.75

SJ300–007HFU/E

20

1.25

10A

10A

16

14

1.25

20

1.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1.5

SJ300–015HFU/E

18

2

10A

10A

16

14

1.25

18

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

2.2

SJ300–022HFU/E

16

2

10A

10A

16

14

1.25

16

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

4.0

SJ300–040HFU/E

14

2

15A

15A

16

14

1.25

14

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

5.5

SJ300–055HFU/E

12

2

15A

15A

14

14

2

12

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

7.5

SJ300–075HFU/E

10

3.5

20A

20A

10

12

3.5

10

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

11

SJ300–110HFU/E

8

5.5

30A

30A

8

10

5.5

8

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

15

SJ300–150HFU/E

6

8

40A

40A

8

10

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

18.5

SJ300–185HFU/E

6

14

50A

50A

4

10

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

22

SJ300–220HFU/E

4

14

60A

60A

4

10

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

30

SJ300–300HFU/E

3

22

70A

70A

3

10

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

37

SJ300–370HFU/E

1

14 14

90A

90A

3

8

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

45

SJ300–450HFU/E

1 AWG

38

125A

125A

1

8

22

 

 

 

 

 

(75°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

55

SJ300–550HFU/E

1/0 1/0

22 22

125A

125A

1

6

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

75

SJ300–750HFU/E

3/0 (1/0

30 30

175A

175A

1/0

6

50

 

 

 

 

 

1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125

90

SJ300–900HFU/E

3/0 (1/0

38 38

200A

200A

3/0

6

80

 

 

 

 

 

1/0

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

110

SJ300–1100HFU/E

1/0 1/0

50 50

250A

250A

3/0

4

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

175

132

SJ300–1320HFE

3/0 3/0

80 80

300A

300A

4/0

4

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

150

SJ300–1500HFU

3/0 3/0

80 80

300A

300A

4/0

4

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1: Field wiring must be made by a UL-listed and CSA certified ring lug terminal connector sized for the wire gauge involved. The connector must be fixed by using the crimping tool specified by the connector manufacturer.

Note 2: Be sure to consider the capacity of the circuit breaker to be used.

Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft (20m).