SJ300 Inverter
Determining wire and fuse sizes, continued...
Motor |
|
|
|
| Wiring *1 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
Output | 400V |
| Power Lines *3 |
| Chassis Ground | Brake Res. |
|
| |||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Inverter |
|
| Fuse | Breaker |
|
|
|
|
|
|
|
HP | kW | Models | AWG | mm2 | (UL- | AWG, | AWG, | mm2 | AWG | mm2 |
|
| |
| rated, | ( GFI | rec. | UL |
|
| |||||||
|
|
|
|
| class J, | type) *2 |
|
|
|
| MountingInverter Installationand | ||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| 600V) |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 | 0.75 | 20 | 1.25 | 10A | 10A | 16 | 14 | 1.25 | 20 | 1.25 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 | 1.5 | 18 | 2 | 10A | 10A | 16 | 14 | 1.25 | 18 | 2 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 | 2.2 | 16 | 2 | 10A | 10A | 16 | 14 | 1.25 | 16 | 2 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 | 4.0 | 14 | 2 | 15A | 15A | 16 | 14 | 1.25 | 14 | 2 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7.5 | 5.5 | 12 | 2 | 15A | 15A | 14 | 14 | 2 | 12 | 2 |
|
| |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 | 7.5 | 10 | 3.5 | 20A | 20A | 10 | 12 | 3.5 | 10 | 3.5 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 | 11 | 8 | 5.5 | 30A | 30A | 8 | 10 | 5.5 | 8 | 5.5 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20 | 15 | 6 | 8 | 40A | 40A | 8 | 10 | 8 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
25 | 18.5 | 6 | 14 | 50A | 50A | 4 | 10 | 14 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30 | 22 | 4 | 14 | 60A | 60A | 4 | 10 | 14 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40 | 30 | 3 | 22 | 70A | 70A | 3 | 10 | 22 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50 | 37 | 1 | 14 14 | 90A | 90A | 3 | 8 | 22 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 | 45 | 1 AWG | 38 | 125A | 125A | 1 | 8 | 22 | — | — |
|
| |
|
|
| (75°C) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
75 | 55 | 1/0 1/0 | 22 22 | 125A | 125A | 1 | 6 | 30 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 | 75 | 3/0 (1/0 | 30 30 | 175A | 175A | 1/0 | 6 | 50 | — | — |
|
| |
|
|
| 1/0 |
|
|
|
|
|
|
|
|
|
|
|
|
| AWG) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
125 | 90 | 3/0 (1/0 | 38 38 | 200A | 200A | 3/0 | 6 | 80 | — | — |
|
| |
|
|
| 1/0 |
|
|
|
|
|
|
|
|
|
|
|
|
| AWG) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
150 | 110 | 1/0 1/0 | 50 50 | 250A | 250A | 3/0 | 4 | 80 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
175 | 132 | 3/0 3/0 | 80 80 | 300A | 300A | 4/0 | 4 | 100 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
200 | 150 | 3/0 3/0 | 80 80 | 300A | 300A | 4/0 | 4 | 100 | — | — |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1: Field wiring must be made by a
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft (20m).