4–29

SJ300 Inverter

Three-wire

Interface

Operation

The 3-wire interface is an industry standard motor control interface. This function uses two inputs for momentary contact start/stop control, and a third for selecting forward or reverse direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22 [F/R] (Forward/Reverse) to three of the intelligent input terminals. Use momentary contact for Start and Stop. Use a selector switch, such as SPST for the Forward/Reverse input. Be sure to set the operation command selection A002=01 for input terminal control of motor.

If you have a motor control interface that needs logic-level control (rather than momentary pulse control), use the [FW] and [RV] inputs instead.

Opt.

 

Symbol

Function Name

Input

 

 

 

 

 

Description

 

 

 

 

 

Code

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

STA

Start Motor

ON

Start motor rotation on momentary

 

 

 

 

 

 

contact (uses acceleration profile)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No change to motor operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

STP

Stop Motor

ON

No change to motor operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Stop motor rotation on momentary contact

 

 

 

 

 

 

(uses deceleration profile)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

F/R

Forward/Reverse

ON

Select reverse direction of rotation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Select forward direction of rotation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

 

C001, C002, C003, C004,

Example: (Requires input configuration—

inputs:

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

 

A002=01

 

see page 4–12.)

 

STP

 

 

 

 

 

settings:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F/R

 

 

STA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

FW

8

CM1

5

3

1

 

The STP logic is inverted. Normally the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

 

6

 

4

 

2

 

 

switch will be closed, so you open the switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to stop. In this way, a broken wire causes the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor to stop automatically (safe design).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When you configure the inverter for 3-wire interface control, the dedicated [FW] terminal is automatically disabled. The [RV] intelligent terminal assignment is also disabled.

See I/O specs on page 4–9.

The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive input; an OFF-to-ON transition gives the Start command. The control of direction is level- sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level- sensitive input.

[STA] terminal

[STP] terminal

[F/R] terminal

Motor revolution speed

 

 

 

 

 

 

 

 

 

 

Forward

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse

Operations Monitoring and

t