4–18

Using Intelligent Input Terminals

Set Second orThird Motors

Operations and Monitoring

If you assign the [SET] or [SET3] functions to an intelligent input terminal, you can select between two or three sets of motor parameters. You may assign one or both of these functions. These second and third parameters store alternate sets of motor characteristics. When terminal [SET] or [SET3] is turned ON, the inverter will use the second or third set of parameters accordingly, generating the frequency output to the motor. When changing the state of the [SET] or [SET3] input terminal, the change will not take effect until the inverter is stopped.

When you turn ON the [SET] or [SET3] input, the inverter operates per the second or third set of parameters, respectively. When the terminal is turned OFF, the output function returns to the original settings (first set of motor parameters). Refer to “Configuring the Inverter for Multiple Motors” on page 4–72 for details.

Opt.

 

Symbol

Function Name

Input

 

 

 

 

 

Description

 

 

 

 

 

 

Code

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

 

 

SET

Set 2nd Motor

ON

causes the inverter to use the 2nd set of

 

 

 

 

 

 

motor parameters for generating the

 

 

 

 

 

 

frequency output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

causes the inverter to default to the 1st

 

 

 

 

 

 

(main) set of motor parameters for gener-

 

 

 

 

 

 

ating the frequency output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

SET3

Set 3rd Motor

ON

causes the inverter to use the 3rd set of

 

 

 

 

 

 

motor parameters for generating the

 

 

 

 

 

 

frequency output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

causes the inverter to default to the 1st

 

 

 

 

 

 

(main) set of motor parameters for gener-

 

 

 

 

 

 

ating the frequency output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

 

C001, C002, C003, C004,

Example: (Requires input configuration—

inputs:

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

 

(none)

 

see page 4–12.)

 

 

 

SET

 

 

 

settings:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

FW

8

 

CM1

5

 

3

1

 

If the terminal state is changed while the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

inverter is running, the inverter continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

using the current set of parameters until the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter is stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If both SET and SET3 are ON at the same time, SET prevails and the 2nd motor parameters are in effect.

See I/O specs on page 4–9.