4–35

SJ300 Inverter

Overload Restriction

The inverter constantly monitors the motor current during acceleration, deceleration, and constant speed. If the inverter reaches the overload restriction level, it adjusts the output frequency automatically to limit the amount of overload. This function prevents an over-current trip by inertia during rapid acceleration or large changes in load at constant speed. It also attempts to prevent an over-voltage trip on deceleration due to regeneration. It accomplishes this by temporarily suspending deceleration and/or increasing the frequency in order to dissipate regenerative energy. Once the DC bus voltage falls sufficiently, deceleration will resume.

OLR Parameter Selection – Two sets of overload restriction parameter settings and values are available as outlined in the table below. Use the B021—B026 group of settings to configure the two set of parameters as needed. By assigning the Overload Restriction function [OLR] to an intelligent terminal, you can select the set of restriction parameters that is in effect.

Function

Function Code

Data or Range

Description

 

 

Set 1

Set 2

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload Restriction

B021

B024

00

Disable

Operation Mode

 

 

 

 

 

 

01

Enabled during accel

 

 

 

 

 

 

 

and constant speed

 

 

 

 

 

 

 

 

02

Enabled during constant

 

 

 

 

speed

 

 

 

 

 

 

 

 

03

Enabled during accel,

 

 

 

 

constant speed, and

 

 

 

 

decel

 

 

 

 

 

Overload Restriction

B022

B025

Rated current * 0.5

Current value at which

Setting

 

 

to rated current * 2

the restriction begins

 

 

 

 

 

Deceleration Rate at

B023

B026

0.1 to 30 seconds

Deceleration time when

Overload Restriction

 

 

 

overload restriction

 

 

 

 

operates

 

 

 

 

 

Opt.

 

Symbol

Function Name

 

Input

 

 

 

 

 

 

Description

 

 

 

 

Code

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

 

OLR

Overload Restric-

 

ON

Selects Overload Restriction Set 2,

 

 

 

tion Selection

 

 

B024, B025, B026 settings in effect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Selects Overload Restriction Set 1,

 

 

 

 

 

 

B021, B022, B023 settings in effect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example: (Requires input configuration—

 

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

B021, B022, B023 (Mode 1),

see page 4–12.)

 

 

 

 

 

 

 

 

 

 

 

 

settings:

 

B024, B025, B026 (Mode 2)

 

 

 

 

 

 

 

 

 

 

 

OLR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

FW

8

 

CM1

5

 

3

 

1

 

If the overload restriction constant (B023 or

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

B026) is set too short, an over-voltage trip

 

 

 

 

 

 

during deceleration will occur due to regener-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ative energy from the motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When an overload restriction occurs during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

acceleration, the motor will take longer to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reach the target frequency, or may not reach

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

it. The inverter will make the following

 

See I/O specs on page 4–9.

 

 

 

 

adjustments:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a)Increase the acceleration time