SJ300 Inverter

4–21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Trip

When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code

 

E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of

 

the error depends on what you connect to the [EXT] terminal. Even if [EXT] is turned OFF, the

 

inverter remains in the trip state. You must reset the inverter or cycle power to clear the error,

 

returning the inverter to the Stop Mode.

 

 

 

 

 

 

 

 

 

 

In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter

 

lets the motor free-run to a stop, and the alarm output turns ON immediately. When the

 

operator initiates a Reset command, the alarm and error are cleared. When the Reset is turned

 

OFF, the motor begins rotation since the Run command is already active.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[EXT]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor revolution speed

 

 

 

 

 

free run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[RS]

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm output terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[FW, RV]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

Opt.

 

Symbol

Function Name

Input

 

 

 

 

 

Description

 

 

 

 

Code

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

EXT

External Trip

ON

When assigned input transitions OFF to

 

 

 

 

 

ON, inverter latches trip event and

 

 

 

 

 

displays E12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No trip event for ON to OFF, any recorded

 

 

 

 

 

trip events remain in history until Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

C001, C002, C003, C004,

Example: (Requires input configuration—

inputs:

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

(none)

 

see page 4–12.)

 

 

 

 

 

 

 

 

 

 

 

 

settings:

 

 

 

 

 

 

 

 

 

 

 

 

 

EXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH

FW

8

 

CM1

5

 

3

 

1

 

If the USP (Unattended Start Protection)

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

feature is in use, the inverter will not automat-

 

 

 

 

 

 

ically restart after cancelling the EXT trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

event. In that case, it must receive either

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

another Run command (OFF-to-ON transi-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion), a keypad Reset command, or an [RS]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

intelligent terminal input signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See I/O specs on page 4–9.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations Monitoring and