3–60

“C” Group: Intelligent Terminal Functions

Analog SignalCalibration

Settings

The functions in the following table configure the signals for the analog output terminals. Note that these settings do not change the current/voltage or sink/source characteristics – only the zero and span (scaling) of the signals.

NOTE: See additional settings for analog calibration: Parameter B080 [AM] Terminal Analog Meter Adjustment (gain), parameter B081 [FM] Terminal Analog Meter Adjustment (gain).

 

 

 

 

 

 

 

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

 

 

 

 

 

Edit

–FE

–FU

 

–FR

 

 

 

 

 

 

 

Name

Description

 

 

 

 

 

 

 

Code

 

 

 

 

 

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C081

[O] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C081 O-ADJUST

 

 

 

tion

 

 

 

 

 

 

 

TOP

02119

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C082

[OI] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C082 OI-ADJUST

ConfiguringDrive Parameters

 

 

 

tion

 

 

 

 

 

 

 

TOP

02512

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C083

[O2] input span calibra-

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C083 O2-ADJUST

 

 

 

 

 

tion

 

 

 

 

 

 

 

TOP

02818

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C085

Thermistor input tuning

Range is 0.0 to 1000

✔ ✔

105.0

105.0

 

105.0

>C085 THERM

 

 

 

(gain)

 

 

 

 

 

 

 

ADJUST

0105.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C086

[AM] terminal offset

Range is 0.0 to 10.0V

✔ ✔

0.0

0.0

 

0.0

V

>C086 AM-MONITOR

 

 

 

tuning

 

 

 

 

 

 

 

OFFSET

00.0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C087

[AMI] terminal meter

Range is 0.0 to 250%

✔ ✔

80.

80.

 

80.

%

>C087 AMI-MON

 

 

 

tuning

 

 

 

 

 

 

 

ADJUST

080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C088

[AMI] terminal offset

Range is 0 to 20mA

✔ ✔

4.0

4.0

 

4.0

mA

>C088 AMI-MON

 

 

 

tuning

 

 

 

 

 

 

 

OFFSET

04.0mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C121

[O] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C121 O-ADJUST

 

 

 

tion

 

 

 

 

 

 

 

ZERO

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C122

[OI] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C122 OI-ADJUST

 

 

 

tion

 

 

 

 

 

 

 

ZERO

00000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C123

[O2] input zero calibra-

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C123 O2-ADJUST

 

 

 

tion

 

 

 

 

 

 

 

ZERO

03622

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not change these settings unless absolutely necessary. Note that if you restore factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

defaults for all parameters, these settings will not change.