3–59

SJ300 Inverter

Serial Communications

The following table configures the communications port of the SJ300 inverter. You can have up to thirty-two devices on the serial communications network. The inverters are slaves and the computer or digital operator is the master. Thus, all inverters on the serial connection must use the same baud rate, data length, parity, and stop bits. However, each device on the serial network must have a unique node address. See “Serial Communications” on page B–1 for more information.

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

Func.

 

 

 

Edit

–FE

–FU

 

–FR

Name

 

Description

 

 

 

 

Code

 

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C070

Data command method

Four option codes:

✘ ✘

02

02

 

02

>C070 PARAM

 

 

02

Digital operator

 

 

 

 

 

 

SELECT

REM

 

 

 

 

 

 

 

 

 

 

 

 

03

RS485

 

 

 

 

 

 

 

 

 

 

04

Expansion card #1

 

 

 

 

 

 

 

 

 

 

05

Expansion card #2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C071

Communication speed

Five option codes:

✘ ✔

04

04

 

04

bps

>C071 RS485

 

selection

02

(Test)

 

 

 

 

 

 

BAU

4800bps

 

 

 

 

 

 

 

 

 

 

 

03

2400bps

 

 

 

 

 

 

 

 

 

 

04

4800bps

 

 

 

 

 

 

 

 

 

 

05

9600bps

 

 

 

 

 

 

 

 

 

 

06

19200bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C072

Node allocation

Set the address of the

✘ ✔

1.

1.

 

1.

>C072 RS485

 

 

inverter on the network.

 

 

 

 

 

 

ADDRESS

01

 

 

 

 

 

 

 

 

 

 

 

 

Range is 1 to 32.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C073

Communication data

Two option codes:

✘ ✔

7

7

 

7

>C073 RS485

 

length selection

07

7-bit data

 

 

 

 

 

 

BIT

7BIT

 

 

 

 

 

 

 

 

 

 

 

08

8-bit data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C074

Communication parity

Three option codes:

✘ ✔

00

00

 

00

>C074 RS485

 

selection

00

No parity

 

 

 

 

 

 

PARITY

NO

 

 

 

 

 

 

 

 

 

 

 

01

Even parity

 

 

 

 

 

 

 

 

 

 

02

Odd parity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C075

Communication stop bit

Two option codes:

✘ ✔

1

1

 

1

>C075 RS485

 

selection

01

1 stop bit

 

 

 

 

 

 

STOPBIT

1BIT

 

 

 

 

 

 

 

 

 

 

 

02

2 stop bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C078

Communication wait

Time the inverter waits after

✘ ✔

0.

0.

 

0.

>C078 RS485

 

time

receiving a message before it

 

 

 

 

 

 

WAIT

0000ms

 

 

 

 

 

 

 

 

 

 

 

transmits. Range is 0.0 to

 

 

 

 

 

 

 

 

 

 

1000 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

Drive Configuring