SJ300 Inverter

Reset Inverter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is

12 ms

in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON

[RS]

minimum

and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The alarm output will be cleared within 30 ms after the onset of the Reset command.

approx. 30 ms

Alarm output

t

WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.

Opt.

 

Symbol

Function Name

 

Input

 

 

 

 

 

Description

 

 

 

 

 

 

Code

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

RS

Reset Inverter

 

ON

The motor output is turned OFF, the Trip

 

 

 

 

 

 

 

Mode is cleared (if it exists), and powerup

 

 

 

 

 

 

 

reset is applied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Normal power-on operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

 

C001, C002, C003, C004,

Example: (Default input configuration

inputs:

 

 

C005, C006, C007, C008

shown—see page 3–47. Jumper position

 

 

 

 

 

 

 

shown is for –xFU/-xFR models; for –xFE

Required

 

B003, B007, C102, C103

models, see page 4–12.)

 

 

 

 

 

 

settings:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

TH

FW

8

CM1

5

3

 

1

 

When the control terminal [RS] input is

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

already ON at powerup for more than 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seconds, the remote operator display is “R-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERROR COMM<2>” (the display of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

digital operator is – – – –). However, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter has no error. To clear the digital

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operator error, turn OFF the terminal [RS]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See I/O specs on page 4–9.

 

 

 

 

input and press one of the operator keys.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The active edge (leading or trailing) of the [RS] signal is determined by the setting of C102.

A terminal configured with the [RS] function can only be configured as a normally open contact. The terminal cannot be used in the normally closed contact state.

When input power is turned ON, the inverter performs the same reset operation as it does when a pulse on the [RS] terminal occurs.