| SJ300 Inverter |
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Output Function Summary Table |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Option | Terminal | Function Name |
| Description |
|
|
| |
| Code | Symbol |
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| 06 | FA3 | Frequency arrival type | ON | when output to motor is at the FA Threshold 1 (C042) |
|
|
| |
|
|
| 3 – at frequency |
| during accel, or at C043 during decel |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the output to motor is not at either the FA |
|
|
| |
|
|
|
|
| Threshold 1 (C042) during accel or at C043 during |
|
|
| |
|
|
|
|
| decel |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 07 | OTQ | ON | when the |
|
|
| ||
|
|
|
|
| is generating excess torque |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the |
|
|
| |
|
|
|
|
| is not generating excess torque |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 08 | IP | Instantaneous power | ON | when the inverter input power has decreased below |
|
|
| |
|
|
| failure signal |
| the acceptable input voltage level |
|
|
| |
|
|
|
|
| Parameters | DriveConfiguring | |||
|
|
|
|
|
|
|
| ||
|
|
|
| OFF | when the inverter input power is within rated range |
| |||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
| 09 | UV | ON | when the inverter input power has decreased below |
|
|
| ||
|
|
|
|
| the acceptable input voltage level |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the inverter input power is within rated range |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 10 | TRQ | In torque limit | ON | when the output torque exceeds level set for the |
|
|
| |
|
|
|
|
| particular torque/frequency quadrant in effect during |
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
| operation |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the output torque is less than the level set for the |
|
|
| |
|
|
|
|
| operating quadrant |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 11 | RNT | Operation time over | ON | when the inverter Run time exceeds the limit set by |
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the inverter Run time is less than the limit set by |
|
|
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
| 12 | ONT | ON | when the inverter |
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the inverter |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 13 | THM | Thermal alarm signal | ON | when the thermal limit for the motor is exceeded |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the thermal limit is not exceeded |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 19 | BRK | Brake release signal | ON | when the inverter signals the external braking system |
|
|
| |
|
|
|
|
| to release (open) its brake |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the inverter is not driving the motor, and needs |
|
|
| |
|
|
|
|
| the external brake engaged |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 20 | BER | Brake error signal | ON | when the output current is less than the set releasing |
|
|
| |
|
|
|
|
| current |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the braking function is not in use, or when the |
|
|
| |
|
|
|
|
| output current to the motor is correct and it is safe to |
|
|
| |
|
|
|
|
| release the brake |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 21 | ZS | Zero speed detect | ON | when the encoder pulses of the motor has stopped |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when motor rotation causes encoder pulses |
|
|
| |
|
|
|
|
|
|
|
|
| |
| 22 | DSE | Speed deviation | ON | when the velocity error exceeds the error threshold |
|
|
| |
|
|
| maximum |
| defined for the encoder input |
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
| OFF | when the velocity error is less than the error threshold |
|
|
| |
|
|
|
|
| defined for the encoder input |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|