Output FunctionAdjustment

Parameters

The following parameters work in conjunction with the intelligent output function, when configured. The overload level parameter (C041) sets the motor current level at which the overload signal [OL] turns ON. The range of settings is from 0% to 200% of the rated current for the inverter. This function is for generating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).

The frequency arrival signal, [FA1] to [FA5], is intended to indicate when the inverter output has reached (arrived at) the target frequency. You can adjust the timing of the leading and trailing edges of the signal via two parameters specific to acceleration and deceleration ramps, C042 and C043.

The Error for the PID loop is the magnitude (absolute value) of the difference between the Setpoint (desired value) and Process Variable (actual value). The PID output deviation signal [OD] (output terminal function option code

04)indicates when the error magnitude has exceeded a magnitude you define.

Motor

current

Overload

signal 1 0

Output

frequency

Arrival signal

1

0

PID Error

(PV-SP)

Deviation

Signal

1

0

C041

t

C042

C043

 

t

SP

C044

t

Parameters

Drive Configuring

 

 

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

 

Name

Description

 

 

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C040

Overload signal output

Choose when the overload

✘ ✔

01

01

 

01

>CO40 OL

 

 

 

mode

signal is enabled; two option

 

 

 

 

 

 

Mode

CRT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

codes:

 

 

 

 

 

 

 

 

 

 

 

 

00 During accel / decel /

 

 

 

 

 

 

 

 

 

 

 

 

const. speed

 

 

 

 

 

 

 

 

 

 

 

 

01 During constant speed

 

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C041

Overload level setting 1

Range is 0.00 * rated current

✘ ✔

Rated current for

A

>C041 OL

 

 

 

 

to 2.00 * rated current

 

each inverter

 

LEVEL

0016.5A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C042

Frequency arrival

Sets the frequency arrival

✘ ✔

0.00

0.00

 

0.00

Hz

>C042 ARV

 

 

 

setting for acceleration

setting threshold for the

 

 

 

 

 

 

ACC

0000.00Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency during

 

 

 

 

 

 

 

 

 

 

 

 

acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C043

Arrival frequency

Sets the frequency arrival

✘ ✔

0.00

0.00

 

0.00

Hz

>C043 ARV

 

 

 

setting for deceleration

setting threshold for the

 

 

 

 

 

 

DEC

0000.00Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency during

 

 

 

 

 

 

 

 

 

 

 

 

deceleration