4–59

SJ300 Inverter

Analog Input Operation

Input Terminal Signals

The SJ300 inverters provide for an external analog

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

O2

AM

FM

input to command the inverter frequency output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value. The analog input terminal group includes

 

 

 

 

L

 

O

OI

AMI

 

the [L], [OI], [O], [O2], and [H] terminals on the

A GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control connector, which provide for Voltage [O]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+V Ref.

 

 

 

 

 

 

 

 

and [O2] or Current [OI] input. All analog input

 

 

 

 

 

 

 

 

signals must use the analog ground [L].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0—10V input

 

 

 

 

 

 

 

If you use either the voltage or current analog

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input, you must select one of them using the logic

-10 / 0 / +10V

 

 

 

 

 

 

 

input terminal function [AT] analog type. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal [AT] is OFF, the voltage input [O] can

4—20mA input

 

 

 

 

 

 

 

command the inverter output frequency. If terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[AT] is ON, the current input [OI] can command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the inverter output frequency. The [AT] terminal function is covered in “Analog Input Current/ Voltage Select” on page 4–26. Remember that you must also set A001 = 01 to select analog input as the frequency source.

 

 

 

 

 

 

 

 

 

O2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A005

 

 

 

 

A001=01

 

 

 

 

 

 

 

 

 

OI

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Terminals

1

 

 

 

 

source setting

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

0

 

 

 

 

 

 

 

(Keypad)

 

 

 

 

Frequency setting

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

O2

AM

FM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

V – I select

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

O

OI

AMI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-20 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT=ON

 

 

A005=00

 

 

 

 

 

 

 

 

 

 

O2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-10 / 0 / +10V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT=ON

 

 

A005=01

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 – 10V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT=OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Filter

Parameter A016 adjusts an analog input sampling filter that evenly affects all analog inputs

 

shown above. The parameter range is from 1 to 30. Before increasing the filter setting, we

 

recommend trying to find the cause of input analog noise. Check for the following:

Look for nearby high-current wiring—avoid any parallel runs to the analog signal wires

Check the impedance between the chassis grounds of the inverter and the analog signal source equipment—a good connection will have a low impedance

Check the analog signal ground impedance from the inverter to the analog signal source

Avoid ground loops... measure the current (or voltage drop) on the chassis ground and signal ground connections; the ideal value is zero

After taking steps to minimize the analog signal noise sources, increase the filter time constant (A016) until the motor output frequency (when commanded by analog inputs) becomes stable.