Setting Motor Constants for Vector Control
Operations and Monitoring
With vector control, the inverter uses the output current, output voltage, and motor constants to estimate the motor torque and speed. It is possible to achieve a high starting torque and accurate speed control at low frequency
•Sensorless Vector Control – improved torque control at output frequencies down to 0.5 Hz. Use A044=03 (1st motor) or A244=03 (2nd motor) to select sensorless vector control.
•Sensorless Vector Control, 0Hz Domain – improved torque control at output frequencies from 0 to 2.5 Hz. Use A044=04 (1st motor) or A244=04 (2nd motor). For this vector control method, we recommend using a motor that is one frame size smaller than the inverter size.
•Sensorless Vector Control with Feedback – improved torque control at all speeds, while providing the most accurate speed regulation
If you do use any vector control methods, it is important that the motor constants stored in the inverter match the motor. We recommend first using the
CAUTION: If the inverter capacity is more than twice the capacity of the motor in use, the inverter may not achieve its full performance specifications.
Operation Status | Symptom | Adjustment | Parameter |
|
|
|
|
|
|
|
|
Powered running | When the speed deviation | Slowly increase the motor constant | H021 / H221 |
| is negative | R2 in relation to |
|
|
| within 1 to 1.2 times preset R2 |
|
|
|
|
|
| When the speed deviation | Slowly decrease the motor constant | H021 / H221 |
| is positive | R2 in relation to |
|
|
| within 0.8 to 1 times preset R2 |
|
|
|
|
|
Regeneration | When low frequency (a | Slowly increase the motor speed | H020 / H220 |
(status with a decel- | few Hz) torque is insuffi- | constant R1 in relation to auto- |
|
erating torque) | cient | tuning data within 1 to 1.2 times R1 |
|
|
|
|
|
|
| Slowly increase the motor constant | H023 / H223 |
|
| IO in relation to |
|
|
| within 1 to 1.2 times preset IO |
|
|
|
|
|
During acceleration | A sudden jerk at start of | Increase motor constant J slowly | H024 / H224 |
| rotation | within 1 to 1.2 times the preset |
|
|
| constant |
|
|
|
|
|
During deceleration | Unstable motor rotation | Decrease the speed response | H05, H205 |
|
|
|
|
|
| Set motor constant J smaller than | H024, H224 |
|
| the preset constant |
|
|
|
|
|
During torque | Insufficient torque during | Set the overload restriction level | B021, |
limiting | torque limit at low speed | lower than the torque limit level | B041 to B044 |
|
|
|
|
At | Irregular rotation | Set motor constant J larger than the | H024, H244 |
operation |
| preset constant |
|
|
|
|
|
When using a motor one frame size smaller than the inverter rating, the torque limit value (B041 to B044) is from the following formula and the value of the actual motor torque limit is calculated by the formula. Do not set a value in B041 to B044 that results in an actual torque greater than 200% or you risk motor failure.
For example, suppose you have a 0.75kW inverter and a 0.4kW motor. The torque limit setting value that is for T=200% is set (entered) as 106%, shown by the following formula:
Torque limit setting = | ⋅ | Motor capacity- | = | 200% ⋅ 0.4kW | = | 106% | |
| |||||||
| Inverter capacity |
| 0.75kW |
|
|