SJ300 Inverter
Troubleshooting The table below lists typical symptoms and the corresponding solution(s).
TipsSymptom/condition | Probable Cause | Solution | ||
|
|
|
|
|
|
|
|
|
|
|
|
| • Is the frequency command source | • Make sure the parameter |
|
|
| A001 parameter setting correct? | setting A001 is correct. |
|
|
| • Is the Run command source A002 | • Make sure the parameter |
|
|
| parameter setting correct? | setting A002 is correct. |
|
|
|
|
|
|
|
| • Is power being supplied to terminals | • Check terminals [R], [S], and |
|
|
| [R], [S], and [T] ([L1], [L2], and | [T] ([L1], [L2], and [L3]), then |
|
|
| [L3])? If so, the POWER lamp should | [U], [V], and [W] ([T1], [T2], |
|
|
| be ON. | and [T3]). |
|
|
|
| • Turn ON the power supply or |
|
|
|
| check fuses. |
|
|
|
|
|
|
|
| • Is there an error code EXX.X displayed? | • Press the FUNC. key and deter- |
|
| The inverter |
| mine the error type. Eliminate |
|
|
| the error cause, then clear the | |
|
| outputs U, V, W |
| error (Reset). |
|
| are not supplying |
|
|
The motor |
| • Are the signals to the intelligent input | • Verify the terminal functions | |
| voltage. | |||
will not run. |
| terminals correct? | for C001 - C008 are correct. | |
|
|
| • Is the Run Command active? | • Turn ON Run command |
|
|
|
| enable. |
|
|
| • Is the [FW] terminal (or [RV]) | • Supply 24V to [FW] or [RV] |
|
|
| connected to P24 (via switch, etc.) | terminal, if configured. |
|
|
|
|
|
|
|
| • Has the frequency setting for F001 | • Set the parameter for F001 to a |
|
|
| been set greater than zero? | safe, |
|
|
| • Are the control circuit terminals [H], | • If the potentiometer is the |
|
|
| [O], and [L] connected to the potenti- | frequency setting source, verify |
|
|
| ometer? | voltage at [O] > 0V. |
|
|
|
|
|
|
|
| • Is the RS (reset) function or FRS (free- | • Turn OFF the command(s). |
|
|
| run stop) function ON? |
|
|
|
|
|
|
|
| Inverter outputs | • Is the motor load too heavy? | • Reduce load or test the motor |
|
| U, V, W are |
| independently of the load. |
|
| supplying voltage. |
|
|
|
|
|
|
|
|
|
| • Are the connections of output termi- | • Make connections according to |
|
|
| nals [U/T1], [V/T2], and [W/T3] | the phase sequence of the |
|
|
| correct? | motor. In general: |
The direction of the motor is | • Is the phase sequence of the motor | FWD = | ||
forward or reverse with respect to | ||||
| reversed. | [U/T1],[V/T2], and [W/T3]? |
| |
|
|
|
| |
|
|
|
|
|
|
|
| • Are the control terminals [FW] and | • Use terminal [FW] for forward, |
|
|
| [RV] wired correctly? | and [RV] for reverse. |
|
|
| • Is parameter F004 properly set? | • Set motor direction in F004. |
|
|
|
|
|
Troubleshooting Maintenance and