B–15

SJ300 Inverter

Command – 08 The 08 command initializes the inverter parameters to the factory default values. First, you must set B84 (use command 07) to specify whether you want to clear the trip history at the same time. Also, set B85 to specify the country code for the initialization (use command 07).

The frame format of command 08 follows the

 

Frame format

 

diagram and specification table.

 

 

 

 

 

 

 

 

 

 

 

STX

Node

Command

BCC

[CR]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Element

Description

 

Size

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

BAppendix

 

 

 

 

 

 

 

 

 

 

 

STX

Control code (STart of TeXt)

 

1 byte

STX (0x02)

 

 

 

 

 

 

 

 

 

 

 

 

Node

Node (station) address of inverter

 

2 bytes

01 to 32, and FF (broadcast to all

 

 

 

 

 

 

 

 

 

nodes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

Transmission command

 

2 bytes

08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BCC

Block check sum code

 

2 bytes

Exclusive OR of Node,

 

 

 

 

 

 

 

Command, and Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[CR]

Control code (carriage return)

 

1 byte

[CR] (0x0D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command – 09 The 09 command verifies whether or not it is possible to set a particular parameter in the EEPROM. The frame format of command 08 follows the diagram and specification table.

Transmit frame format

STX Node Command BCC [CR]

 

Element

Description

 

Size

 

 

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STX

Control code (STart of TeXt)

 

1 byte

 

STX (0x02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node

Node (station) address of inverter

2 bytes

 

01 to 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

Transmission command

 

2 bytes

09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BCC

Block check sum code

 

2 bytes

 

Exclusive OR of Node,

 

 

 

 

 

 

 

 

Command, and Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[CR]

Control code (carriage return)

 

1 byte

 

[CR] (0x0D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The receive frame includes an ACK

Receive frame format

 

 

 

 

 

(acknowledge) character, followed by a

 

 

 

 

 

 

 

 

 

 

 

2-byte data field with the result.

STX

Node

 

ACK

 

Data

BCC

[CR]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Element

Description

 

Size

 

 

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STX

Control code (STart of TeXt)

 

1 byte

 

STX (0x02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node

Node (station) address of inverter

2 bytes

 

01 to 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACK

Control code (ACKnowledge)

 

1 byte

 

ACK (0x06)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

Parameter value

 

2 bytes

 

00 = setting not allowed,

 

 

 

 

 

 

 

 

01 = setting is allowed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BCC

Block check sum code

 

2 bytes

 

Exclusive OR of Node,

 

 

 

 

 

 

 

 

Command, and Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[CR]

Control code (carriage return)

 

1 byte

 

[CR] (0x0D)