6–16

Maintenance and Inspection

The figure below shows measurement locations for voltage, current, and power measurements listed in the table on the previous page. The voltage to be measured is the fundamental wave effective voltage. The power to be measured is the total effective power.

 

 

 

 

 

Three-phase measurement diagram

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

L1

 

I1

 

 

 

 

R

U

 

 

I1

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

W01

 

 

 

 

 

 

EU-V

W01

L2

 

I2

 

 

 

 

S

V

 

 

I1

 

 

 

 

T2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

W02

 

 

 

 

 

 

EU-V

W02

L3

 

I3

 

 

 

 

T

W

 

 

I1

 

 

 

 

 

T3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

 

 

 

 

 

 

 

 

EU-V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter Output Voltage Measurement Techniques

Taking voltage measurements around drives equipment requires the right equipment and a safe approach. You are working with high voltages and high-frequency switching waveforms that are not pure sinusoids. Digital voltmeters will not usually produce reliable readings for these waveforms. And, it is usually risky to connect high voltage signals to oscilloscopes. The inverter output semiconductors have some leakage, and no-load measurements produce misleading results. So, we highly recommend using the following circuits to measure voltage for performing the equipment inspections.

Troubleshooting and Maintenance

 

 

 

 

Voltage measurement with load

 

Voltage measurement without load

 

 

 

 

 

 

 

 

 

 

L1/R

 

 

 

 

U/T1

 

 

L1/R

 

 

U/T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2/S

 

Inverter

V/T2

 

 

 

 

L2/S

 

 

Inverter

 

V/T2

 

 

 

L3/T

 

 

W/T3

 

 

 

L3/T

 

 

 

 

W/T3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V class

 

Diode bridge

Voltmeter

 

V class

 

Diode bridge

Voltmeter

200V class

 

600V 0.01A min.

300V range

 

200V class

 

600V 0.01A min.

300V range

400V class

 

1000V 0.1 A min.

600V range

 

400V class

 

1000V 0.1 A min.

600V range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working with the inverters and taking measurements. Be sure to place the measurement circuitry above in an insulated housing before using them.