3–23

SJ300 Inverter

Automatic

Voltage

Regulation (AVR)Function

The automatic voltage regulation (AVR) feature keeps the inverter output voltage at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage disturbances. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage. If you enable this feature, be sure to select the proper voltage class setting for your motor.

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

 

 

Name

Description

 

 

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A081

AVR function select

Automatic (output) voltage

✘ ✘

00

00

 

00

>A081 AVR

 

 

 

 

 

regulation, selects from

 

 

 

 

 

 

MODE

DOFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

three type of AVR functions,

 

 

 

 

 

 

 

 

 

 

 

 

three option codes:

 

 

 

 

 

 

 

 

 

 

 

 

00 AVR enabled

 

 

 

 

 

 

 

 

 

 

 

 

01 AVR disabled

 

 

 

 

 

 

 

 

 

DriveConfiguring Parameters

 

 

02 AVR enabled except

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

during deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A082

AVR voltage select

200V class inverter settings:

✘ ✘

230/

230/

 

200/

V

>A082 AVR

 

 

 

 

 

200/215/220/230/240

 

400

460

 

400

 

AC

230

 

 

 

 

 

 

 

 

 

 

 

 

 

400V class inverter settings:

 

 

 

 

 

 

 

 

 

 

 

 

380/400/415/440/460/

 

 

 

 

 

 

 

 

 

 

 

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy SavingsMode / OptimalAccel/Decel

Energy Savings Mode – This function allows the inverter to deliver the minimum power necessary to maintain speed at any given frequency. This works best when driving variable torque characteristic loads such as fans and pumps. Parameter A085=01 enables this function and A086 controls the degree of its effect. A setting of 0.0 yields slow response but high accuracy, while a setting of 100 will yield a fast response with lower accuracy.

 

 

 

 

 

 

 

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

 

 

 

 

 

Edit

–FE

–FU

 

–FR

 

 

 

 

 

 

Name

 

Description

 

 

 

 

 

 

 

Code

 

 

 

 

 

 

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A085

Operation mode

 

Three options:

✘ ✘

00

00

 

00

>A085 RUN

 

 

 

 

 

selection

 

00 Normal operation

 

 

 

 

 

 

MODE

NOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 Energy-saver operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02 Optimal accel/decel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A086

Energy saving mode

 

Range is 0.0 to 100 sec.

✔ ✔

50.0

50.0

 

50.0

sec.

>A086 RUN

 

 

 

 

 

tuning

 

 

 

 

 

 

 

 

ECO

0050.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optimal Accel/Decel Operation – This feature uses “fuzzy” logic to optimize acceleration

 

 

 

 

 

 

 

 

 

and deceleration curves in real time. It is enabled by A085=02. Optimal accel/decel operation

 

 

 

 

 

 

 

 

 

automatically adjusts the acceleration and deceleration times in response to changes in load or

 

 

 

 

 

 

 

 

 

inertia to take advantage of the maximum output current capability of the inverter. In general,

 

 

 

 

 

 

 

 

 

optimal accel/decel will allow for the shortest accel and decel times based on the actual load

 

 

 

 

 

 

 

 

 

conditions. The function continuously monitors output current and DC bus voltage to avoid

 

 

 

 

 

 

 

 

 

reaching their respective trip levels.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: In this mode, the settings of acceleration and deceleration times (F002 and F003) are

 

 

 

 

 

 

 

 

 

disregarded.