| SJ300 Inverter |
|
| ||
|
|
|
|
|
|
|
|
|
|
Torque Limit | The Torque Limit function limits the motor output torque for sensorless vector control, sensor- |
|
| ||||||
| less vector control 0Hz domain, or vector control with feedback. |
|
| ||||||
| In the torque limit function, the following operational modes are available (selected by B040): |
|
| ||||||
| 1. |
|
| ||||||
| driving and regenerating, reverse driving and regenerating. Limits for each quadrant are set |
|
| ||||||
| with B041 – B044 individually. |
|
|
|
|
|
| ||
| 2. Terminal selection mode – By use of torque limit select intelligent input terminals 1 and 2, |
|
| ||||||
| this mode changes and uses torque limits 1 – 4 set in B041 – B044. Selected torque limit |
|
| ||||||
| range is valid in all four quadrants. |
|
|
|
|
| |||
| 3. Analog input mode – This mode sets torque limit value by the voltage applied to terminal |
|
| ||||||
| [O2] (referenced to [L] for ground. An input of 0 – 10V corresponds to the torque limit |
|
| ||||||
| value of 0 to 200%. The selected torque limit value is valid in all four quadrants (whether |
|
| ||||||
| forward or reverse move, driving or regenerating). |
|
|
|
|
| |||
| 4. Expansion Cards 1 and 2 – This function is valid when using the expansion card |
|
| ||||||
| Please refer to the |
|
|
|
|
| |||
| When the torque limit enable function [TL] is assigned to an intelligent input terminal, torque |
|
| ||||||
| limiting occurs only when [TL] is ON. When the [TL] input is OFF, the inverter always uses the |
|
| ||||||
| default torque control limit of 200% maximum. That torque limit value corresponds to 200% of |
|
| ||||||
| the maximum inverter output current. Therefore, the output torque also depends on the particu- |
|
| ||||||
| lar motor in use. When the |
|
| ||||||
| tion, it turns ON when the inverter is performing torque limiting. |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| Code | Function |
| Data or Range | Description |
|
|
| |
|
|
|
|
|
|
| Monitoringand |
| |
|
|
|
|
|
|
|
| ||
|
|
|
| 00 | V/f Constant torque |
| Operations | ||
|
|
|
| 01 | V/f Variable torque |
| |||
|
|
|
|
|
|
| |||
| A044 / | Control method |
| 02 | V/f |
|
|
| |
| A244 | selection |
| 03 | Sensorless vector *1 |
|
|
| |
|
|
|
| 04 | Sensorless vector, 0 Hz domain *1 |
|
|
| |
|
|
|
| 05 | Vector control with sensor *2 |
|
|
| |
|
|
|
|
|
|
|
|
| |
| B040 |
|
| 00 |
|
|
| ||
|
|
|
|
| |||||
|
| Torque limit |
| 01 | Terminal selection |
|
|
| |
|
|
| 02 | Analog [O2] input |
|
|
| ||
|
| selection |
|
|
|
| |||
|
|
| 03 | Expansion card 1 |
|
|
| ||
|
|
|
|
|
|
| |||
|
|
|
| 04 | Expansion card 2 |
|
|
| |
|
|
|
|
|
|
|
|
| |
| B041 | Torque limit 1 |
| 0 to 200% |
|
|
| ||
|
|
|
|
|
|
|
|
| |
| B042 | Torque limit 2 |
| 0 to 200% |
|
|
| ||
|
|
|
|
| mode |
|
|
| |
|
|
|
|
|
|
|
|
| |
| B043 | Torque limit 3 |
| 0 to 200% |
|
|
| ||
|
|
|
|
|
|
|
|
| |
| B044 | Torque limit 4 |
| 0 to 200% |
|
|
| ||
|
|
|
|
| mode |
|
|
| |
|
|
|
|
|
|
|
|
| |
| C001 | Intelligent input |
| 40 | Torque limit enable |
|
|
| |
| to | terminal [1] to [8] |
| 41 | Torque limit selection, bit 1 (LSB) |
|
|
| |
| C008 | function |
| 42 | Torque limit selection, bit 2 (MSB) |
|
|
| |
|
|
|
|
|
|
|
|
| |
| C021 | Intelligent output |
| 10 | In torque limit |
|
|
| |
| to | terminal [11] to [15] |
|
|
|
|
|
|
|
| C025 | function |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 1: Unavailable for A344
Note 2: Unavailable for A244 and A344