3–40

“B” Group: Fine-Tuning Functions

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

Name

Description

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B046

Reverse Run protection

Prohibits reverse motor

✘ ✔

00

00

 

00

>b046 LIMIT

 

 

enable

rotation. Two option codes:

 

 

 

 

 

 

PREV

OFF

 

 

 

 

 

 

 

 

 

 

 

00 Disable

 

 

 

 

 

 

 

 

 

 

01 Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive

Parameters

 

 

Controlled Deceleration at Power Loss – When enabled, this feature permits the inverter to control final motor deceleration upon loss of inverter input power. First, you must make a wiring change to the inverter. See “Optional Controlled Decel and Alarm at Power Loss” on page 4–4 for complete instructions including wiring and signal timing diagrams for using the controlled deceleration at power loss feature.

After making the wiring change, use function B050 to enable the feature. Use B051 to determine the point at which a decaying DC bus voltage will trigger the controlled deceleration. Use parameter B054 to specify an initial step-wise deceleration at power loss, and B053 to specify the duration of the linear deceleration.

During the controlled deceleration the inverter itself acts as a load to decelerate the motor. With either a high-inertia load or a short deceleration time (or both), it is possible that the inverter impedance will not be low enough to continue linear deceleration and avoid an over-voltage condition on the DC bus. Use parameter B052 to specify a threshold for the over-voltage. In this case, the inverter pauses deceleration (runs at constant speed). When the DC bus decays again below the threshold, linear deceleration resumes. The pause/resume process will repeat as necessary until the DC bus energy is depleted (under-voltage condition occurs).

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

Func.

 

 

Edit

–FE

–FU

 

–FR

Name

Description

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B050

Controlled deceleration

Allows inverter control

✘ ✘

00

00

 

00

>b050 IPS-DECEL

 

and stop on power loss

using regenerative energy to

 

 

 

 

 

 

Mode

OFF

 

 

 

 

 

 

 

 

 

 

 

decelerate after loss of input

 

 

 

 

 

 

 

 

 

 

power (requires jumper

 

 

 

 

 

 

 

 

 

 

change)

 

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

 

00 Disable

 

 

 

 

 

 

 

 

 

 

01 Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B051

DC bus voltage trigger

Sets trigger for controlled

✘ ✘

0.0

0.0

 

0.0

VDC

>b051 IPS-DECEL

 

level during power loss

deceleration and stop on

 

 

 

 

 

 

V1

0000.0Vdc

 

 

 

 

 

 

 

 

 

 

 

power loss function.

 

 

 

 

 

 

 

 

 

 

Range is 0.0 to 1000.V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B052

Over-voltage threshold

Sets over-voltage threshold

✘ ✘

0.0

0.0

 

0.0

VDC

>b052 IPS-DECEL

 

during power loss

for controlled deceleration

 

 

 

 

 

 

V2

0000.0Vdc

 

 

 

 

 

 

 

 

 

 

 

function.

 

 

 

 

 

 

 

 

 

 

Range is 0.0 to 1000.V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B053

Deceleration time

Range is 0.01 to 99.99 sec. /

✘ ✘

1.00

1.00

 

1.00

sec.

>b053 IPS-DECEL

 

setting during power

100.0 to 999.9 sec. /

 

 

 

 

 

 

TIME

0001.00s

 

 

 

 

 

 

 

 

 

 

loss

1000 to 3600 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B054

Initial output frequency

Sets the initial decrease in

✘ ✘

0.00

0.00

 

0.00

Hz

>b054 IPS-DECEL

 

decrease during power

output frequency upon

 

 

 

 

 

 

DEC-F

00.00Hz

 

 

 

 

 

 

 

 

 

 

loss

power loss.

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 10.00 Hz