“C” Group: Intelligent Terminal Functions
Configuring Drive | Parameters |
|
|
Input Function Summary Table
Option | Terminal | Function Name |
| Description |
Code | Symbol |
| ||
|
|
| ||
|
|
|
|
|
|
|
|
|
|
13 | USP | Unattended Start | ON | On powerup, the inverter will not resume a Run |
|
| Protection |
| command (mostly used in the US) |
|
|
|
|
|
|
|
| OFF | On powerup, the inverter will resume a RUN |
|
|
|
| command that was active before power loss |
|
|
|
|
|
14 | CS | Commercial Power | ON | |
|
| Source |
| motor is already running at powerup (via bypass), |
|
|
|
| thus suppressing the inverter’s motor output in Run |
|
|
|
| Mode |
|
|
|
|
|
|
|
| OFF | |
|
|
|
| time delay (B003), frequency match its output to |
|
|
|
| existing motor speed, and resume normal Run Mode |
|
|
|
| operation |
|
|
|
|
|
15 | SFT | Software Lock | ON | The keypad and remote programming devices are |
|
|
|
| prevented from changing parameters |
|
|
|
|
|
|
|
| OFF | The parameters may be edited and stored |
|
|
|
|
|
16 | AT | Analog Input Voltage/ | ON | If A005=00, terminal [OI] is enabled for input. |
|
| current Select |
| If A005=01, terminal [O2] is enabled for input. |
|
|
|
| (Use terminal [L] for signal return.) |
|
|
|
|
|
|
|
| OFF | Terminal [O] is enabled for voltage input |
|
|
|
| (Use terminal [L] for signal return) |
|
|
|
|
|
17 | SET3 | Set (select) 3rd motor | ON | The inverter uses 3rd motor parameters for generating |
|
| data |
| frequency output to motor |
|
|
|
|
|
|
|
| OFF | The inverter uses 1st (main) motor parameters for |
|
|
|
| generating frequency output to motor |
|
|
|
|
|
18 | RS | Reset Inverter | ON | The trip condition is reset, the motor output is turned |
|
|
|
| OFF, and powerup reset is asserted |
|
|
|
|
|
|
|
| OFF | Normal |
|
|
|
|
|
20 | STA | START | ON | Starts the motor rotation |
|
|
|
| |
|
| OFF | No change to present motor status | |
|
|
| ||
|
|
|
|
|
21 | STP | STOP | ON | Stops the motor rotation |
|
|
|
| |
|
| OFF | No change to present motor status | |
|
|
| ||
|
|
|
|
|
22 | F/R | FWD, REV | ON | Selects the direction of motor rotation: ON = FWD. |
|
|
| While the motor is rotating, a change of F/R will start | |
|
|
|
| a deceleration, followed by a change in direction. |
|
|
|
|
|
|
|
| OFF | Selects the direction of motor rotation: OFF =REV. |
|
|
|
| While the motor is rotating, a change of F/R will start |
|
|
|
| a deceleration, followed by a change in direction. |
|
|
|
|
|
23 | PID | PID Disable | ON | Temporarily disables PID loop control. Inverter |
|
|
|
| output turns OFF as long as PID Enable is active |
|
|
|
| (A071=1). |
|
|
|
|
|
|
|
| OFF | Has no effect on PID loop operation, which operates |
|
|
|
| normally if PID Enable is active (A071 = 1). |
|
|
|
|
|