SJ300 Inverter
Miscellaneous functions, continued...B083: Carrier frequency adjustment – The internal switching frequency of the inverter circuitry (also called the chopper frequency). It is called the carrier frequency because the lower AC output frequency of the inverter “rides” the carrier. The faint,
NOTE: When the inverter is in sensorless vector mode, use B083 to set the carrier frequency greater than 2.1 kHz for proper operation.
NOTE: The carrier frequency setting must stay within specified limits for
B084, B085: Initialization codes – These functions allow you to restore the factory default settings. Please refer to “Restoring Factory Default Settings” on page
B086: Frequency display scaling – You can convert the output frequency monitor on D001 to a scaled number (engineering units) monitored at function D007. For example, the motor may run a conveyor that is monitored in feet per minute. Use this formula:
Scaled output frequency (D007) = Output frequency (D001) ⋅ Factor (B086)
| “B” Function | Run |
| Defaults |
|
|
|
| ||
|
|
| Mode |
|
|
|
| Units | SRW Display | |
|
|
|
|
|
|
| ||||
Func. |
|
| Edit |
| ||||||
Name | Description |
|
|
|
| |||||
Code | Lo Hi | (EU) | (US) |
| (JP) |
|
|
| ||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
B080 | [AM] terminal analog | Adjust | ✔ ✔ | 180 | 180 |
| 180 | — | >b080 | |
| meter adjustment | meter connected to terminal |
|
|
|
|
|
| ADJUST | 180 |
|
|
|
|
|
|
|
|
| ||
|
| [AM], range is 0 to 255 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
B081 | [FM] terminal analog | Adjust | ✔ ✔ | 60 | 60 |
| 60 | — | >b081 | |
| meter adjustment | meter connected to terminal |
|
|
|
|
|
| ADJUST | 060 |
|
|
|
|
|
|
|
|
| ||
|
| [FM], range is 0 to 255 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
B082 | Start frequency adjust- | Sets the starting frequency | ✘ ✔ | 0.50 | 0.50 |
| 0.50 | Hz | >b082 fmin | |
| ment | for the inverter output, range |
|
|
|
|
|
| F | 00.50Hz |
|
|
|
|
|
|
|
|
| ||
|
| is 0.10 to 9.99 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
B083 | Carrier frequency | Sets the PWM carrier (inter- | ✘ ✔ | 5.0 | 5.0 |
| 5.0 | kHz | >b083 CARRIER | |
| setting | nal switching frequency) |
|
|
|
|
|
| F | 05.0kHz |
|
|
|
|
|
|
|
|
| ||
|
| Range is 0.5 to 15.0 kHz, or |
|
|
|
|
|
|
|
|
|
| 0.5 to 10 kHz when derated |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
B084 | Initialization mode | Select the type of initializa- | ✘ ✘ | 00 | 00 |
| 00 | — | >b084 INITIAL | |
| (parameters or trip | tion to occur, three option |
|
|
|
|
|
| MODE | TRP |
|
|
|
|
|
|
|
|
| ||
| history) | codes: |
|
|
|
|
|
|
|
|
|
| 00 Trip history clear |
|
|
|
|
|
|
|
|
|
| 01 Parameter initialization |
|
|
|
|
|
|
|
|
|
| 02 Trip history clear and |
|
|
|
|
|
|
|
|
|
| parameter initialization |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Parameters | Drive Configuring |
|
|