1–7

SJ300 Inverter

Tables for 400V

Note that “General Specifications” on page 1–9 covers all SJ300 inverters, followed by

class inverters

footnotes for all specifications tables. The 400V models in the upper table below (1 to 15 hp)

 

 

include internal dynamic braking units (see “Dynamic Braking” on page 5–6).

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

400V Class Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SJ300 inverters,

 

U.S. version

 

007HFU

015HFU

022HFU

040HFU

055HFU

075HFU

110HFU

400V models

 

 

 

 

 

 

 

 

 

 

 

 

European ver.

007HFE

015HFE

022HFE

040HFE

055HFE

075HFE

110HFE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable motor size

*2

 

HP

1

2

3

5

7.5

10

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

0.75

1.5

2.2

4.0

5.5

7.5

11

 

 

 

 

 

 

 

 

 

 

Rated capacity (400 / 480V) kVA

 

1.7 / 2.0

2.6 / 3.1

3.6 / 4.4

5.9 / 7.1

8.3 / 9.9

11 / 13.3

15.9/19.1

 

 

 

 

 

 

 

 

 

 

 

Rated input voltage

 

 

 

 

3-phase (3-wire) 380 to 480V ±10%, 50/60 Hz ±5%

 

 

 

 

 

 

 

 

 

 

Rated input current (A)

 

2.8

4.2

5.8

9.5

13

18

25

 

 

 

 

 

 

 

 

 

Rated output voltage *3

 

 

3-phase (3-wire): 380 to 480V (corresponding to input voltage)

 

 

 

 

 

 

 

 

 

 

Rated output current (A)

 

2.5

3.8

5.3

8.6

12

16

23

 

 

 

 

 

 

 

 

 

Efficiency at 100% rated output, %

 

89.5

92.3

93.2

94.0

94.4

94.6

94.8

 

 

 

 

 

 

 

 

 

 

Watt loss,

 

at 70% output

76

102

127

179

242

312

435

approximate (W)

 

 

 

 

 

 

 

 

 

 

 

 

at 100% output

88

125

160

235

325

425

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting torque *6

 

 

 

 

200% at 0.5 Hz (SLV), 150% at around 0 Hz (SLV, 0 Hz domain,

 

 

 

 

 

 

with motor one frame size down), 100% at 0 Hz (with feedback board)

 

 

 

 

 

 

 

 

 

 

Dynamic braking

 

internal res. only

50%

 

20%

 

10%

approx. % torque,

 

 

 

 

 

 

 

 

 

 

 

 

with external res.

 

200%

 

140%

100%

70%

short time stop *7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

 

 

 

 

Variable operating frequency, time, and braking force

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

kg / lb

 

3.5 / 7.7

3.5 / 7.7

3.5 / 7.7

3.5 / 7.7

3.5 / 7.7

5 / 11

5 / 11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

400V Class Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SJ300 inverters,

 

U.S. version

 

150HFU

185HFU

220HFU

300HFU

370HFU

450HFU

550HFU

400V models

 

 

 

 

 

 

 

 

 

 

 

 

European ver.

150HFE

185HFE

220HFE

300HFE

370HFE

450HFE

550HFE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable motor size

*2

 

HP

20

25

30

40

50

60

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kW

15

18.5

22

30

37

45

55

 

 

 

 

 

 

 

 

 

 

Rated capacity (400 / 480V) kVA

 

22.1 / 26.6

26.3 / 31.5

33.2 / 39.9

40.1 / 48.2

51.9 / 62.3

62.3 / 74.8

76.2/91.4

 

 

 

 

 

 

 

 

 

 

 

Rated input voltage

 

 

 

 

3-phase (3-wire) 380 to 480V ±10%, 50/60 Hz ±5%

 

 

 

 

 

 

 

 

 

 

Rated input current (A)

 

35

42

53

64

83

99

121

 

 

 

 

 

 

 

 

 

Rated output voltage *3

 

 

3-phase (3-wire): 380 to 480V (corresponding to input voltage)

 

 

 

 

 

 

 

 

 

 

Rated output current (A)

 

32

38

48

58

75

90

110

 

 

 

 

 

 

 

 

 

Efficiency at 100% rated output, %

 

94.9

95.0

95.0

95.1

95.1

95.1

95.1

 

 

 

 

 

 

 

 

 

Watt loss,

 

at 70% output

575

698

820

1100

1345

1625

1975

approximate (W)

 

 

 

 

 

 

 

 

 

 

 

 

at 100% output

800

975

1150

1550

1900

2300

2800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting torque *6

 

 

 

 

200% at 0.5 Hz (SLV), 150% at around 0 Hz (SLV, 0 Hz domain,

 

 

 

 

 

 

with motor one frame size down), 100% at 0 Hz (with feedback board)

 

 

 

 

 

 

 

 

 

Dynamic braking

 

w/o braking unit

 

 

 

10%

 

 

 

approx. % torque,

 

 

 

 

 

 

 

 

 

 

 

 

with braking unit

40–200%

40–200%

35–200%

110–170%

90–150%

70–120%

60–100%

short time stop *7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC braking

 

 

 

 

Variable operating frequency, time, and braking force

 

 

 

 

 

 

 

 

 

 

 

Weight

 

kg / lb

 

12 / 26.4

12 / 26.4

12 / 26.4

20 / 44

30 / 66

30 / 66

50 / 110

 

 

 

 

 

 

 

 

 

 

 

 

Started Getting