4–51

SJ300 Inverter

InstantaneousPower Failure /Under-voltage

Signal

An instantaneous power failure (complete loss) or under-voltage condition (partial loss) of inverter input voltage can occur without warning. SJ300 Series inverters can be configured to respond to these conditions in different ways. You can select whether the inverter trips or retries (restart attempt) when an instantaneous power failure or under-voltage condition occurs. You can select the retry function with parameter B001.

When enabled, the Retry Function operates in the following ways:

Under-voltage conditions – When an instantaneous power failure or under-voltage condi- tion occurs, the inverter will attempt to restart up to 16 times. A trip condition will occur on the 17th attempt, which must be cleared with the Stop/Reset key.

Over-current/voltage conditions – When retry function is selected and an over-current or an over-voltage condition occurs, a restart is attempted 3 times. A trip will occur on the 4th failed restart attempt. Use parameter B004 to select the trip and alarm response to instanta- neous power failure and under-voltage conditions. The following table shows the related parameters to these power fault conditions, and timing diagrams are on the next page.

Code

Function

Data or Range

Description

 

 

 

 

 

 

 

 

B001

Selection of

00

Alarm output after trip, automatic

 

automatic restart

 

restart disabled

 

mode

 

 

 

01

Restart at 0 Hz

 

 

 

 

 

 

 

 

02

Retry with frequency matching to

 

 

 

present motor speed

 

 

 

 

 

 

03

Retry with frequency matching

 

 

 

followed by deceleration to stop—

 

 

 

then trip alarm

 

 

 

 

B002

Allowable under-

0.3 to 1.0 sec.

The amount of time a power input

 

voltage power failure

 

under-voltage can occur without

 

time

 

tripping the power failure alarm. If

 

 

 

under-voltage exists longer than this

 

 

 

time, the inverter trips, even if the

 

 

 

restart mode is selected. If it exists

 

 

 

less than this time retry will be

 

 

 

attempted.

 

 

 

 

B003

Retry wait time

0.3 to 100 sec.

Time delay after a trip condition goes

 

before motor restart

 

away before the inverter restarts the

 

 

 

motor

 

 

 

 

B004

Instantaneous power

00

Disable

 

failure / voltage trip

 

 

 

01

Enable

 

alarm enable

 

 

 

 

 

02

Disable during stop and ramp to stop

 

 

 

 

B005

Number of restarts

00

Restart up to 16 times on instanta-

 

on power failure /

 

neous power failure or under-voltage

 

under-voltage trip

 

 

 

01

Always restart on instantaneous

 

events

 

 

power failure or an under-voltage

 

 

 

 

 

 

condition

 

 

 

 

B007

Restart frequency

0.00 to 400.0 Hz

When frequency of the motor is less

 

threshold

 

than this value, the inverter will

 

 

 

restart at 0 Hz

 

 

 

 

Operations Monitoring and