3–30

“B” Group: Fine-Tuning Functions

 

 

 

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

 

Edit

–FE

–FU

 

–FR

 

 

 

Name

Description

 

 

 

 

 

 

 

Code

 

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B002

Allowable under-

The amount of time a power

✘ ✔

1.0

1.0

 

1.0

sec.

>b002 IPS

 

 

 

voltage power failure

input under-voltage can

 

 

 

 

 

 

TIME

1.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time

occur without tripping the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power failure alarm. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

under-voltage exists longer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than this time, the inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trips, even if the restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode is selected. If it exists

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

less than this time retry will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be attempted. Range is 0.3 to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25.0 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B003

Retry wait time before

Time delay after a trip

✘ ✔

1.0

1.0

 

1.0

sec.

>b003 IPS

 

 

 

motor restart

condition goes away before

 

 

 

 

 

 

WAIT

001.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ConfiguringDrive Parameters

 

 

 

 

 

 

the inverter restarts the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.3 to 100 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B004

Instantaneous power

Three option codes:

✘ ✔

00

00

 

00

>b004 IPS

 

 

 

failure / under-voltage

00 Disable

 

 

 

 

 

 

TRIP

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trip alarm enable

01 Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02 Disable during stop and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ramp to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B005

Number of restarts on

Two option codes:

✘ ✔

00

00

 

00

>b005 IPS

 

 

 

power failure / under-

00 Restart 16 times

 

 

 

 

 

 

RETRY

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage trip events

01 Always restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B006

Phase loss detection

Two option codes:

✘ ✔

00

00

 

00

>b006 PH-FAIL

 

 

 

enable

00 Disable – no trip on

 

 

 

 

 

 

SELECT

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase loss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 Enable – trip on phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

loss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B007

Restart frequency

When the frequency of the

✘ ✔

0.00

0.00

 

0.00

Hz

>b007 IPS

 

 

 

threshold

motor is less than this value,

 

 

 

 

 

 

F

0000.00Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the inverter will restart at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 Hz.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: When a loss of phase occurs, increased ripple current will markedly reduce main

 

 

 

 

 

 

capacitor life over time. Diode bridge failure can also result. If phase loss occurs under load,

 

 

 

 

 

 

the inverter could be damaged. Please pay particular attention to the setting of function B006.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ElectronicThermal OverloadAlarm Setting

The thermal overload detection protects the inverter and motor from overheating due to an excessive load. It uses a current/ inverse time curve to determine the trip point. The thermal overload alarm [THM] is the resulting intelligent output.

First, use B013 to select the torque characteristic that matches your load. This allows the inverter to utilize the best thermal overload characteristic for your application.

Trip current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

factor

 

 

 

Constant torque

 

 

 

 

 

 

B013=01

 

x 1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x 0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reduced

 

 

 

 

 

 

 

 

 

 

 

 

B013=00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x 0.6

 

 

 

 

 

 

 

 

 

torque

 

 

 

 

 

 

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

5

20

60

120

 

 

 

 

 

Output frequency