Troubleshooting
Symptom/condition | Probable Cause |
| Solution | ||
|
|
|
|
| |
|
|
|
|
| |
|
| • If using the analog input, is there | • | Check the wiring. | |
|
| current or voltage at [O] or [OI]? | • Check the potentiometer or | ||
|
|
|
| signal generating device. | |
|
|
|
|
| |
|
| • Is the load too heavy? | • | Reduce the load. | |
|
|
| • Heavy loads activate the | ||
|
|
|
| overload restriction feature | |
The motor speed will not reach the |
|
| (reduces output as needed). | ||
|
|
| |||
• Is the inverter internally limiting the | • Check max frequency setting | ||||
target frequency (desired speed). | |||||
|
| output frequency? |
| (A004) | |
|
|
| • Check frequency upper limit | ||
|
|
|
| setting (A061) | |
|
|
| • If using analog inputs, check | ||
|
|
|
| their settings (A101– A104) | |
|
|
|
| or | |
|
|
|
| A014) | |
|
|
|
| ||
|
| • Is the load fluctuation too great? | • Increase the motor capacity | ||
|
|
|
| (both inverter and motor). | |
The rotation is unstable. | • Is the supply voltage unstable? | • Fix power supply problem. | |||
• Is the problem occurring at a particular | • Change the output frequency | ||||
|
| frequency? |
| slightly, or use the jump | |
|
|
|
| frequency setting to skip the | |
|
|
|
| problem frequency. | |
|
|
|
| ||
The RPM of the motor does not | • Is the maximum frequency setting | • Verify the V/F settings match | |||
A004 correct? |
| motor specifications. | |||
match the inverter output |
| ||||
• Does the monitor function D001 | • Make sure all scaling (such as | ||||
frequency setting. | |||||
display the expected output frequency? |
| A011 to A014) is properly set. | |||
|
|
| |||
|
|
|
| ||
A parameter | True for certain | • Is the inverter in Run Mode? Some | • Put inverter in Stop Mode | ||
parameters | parameters cannot be edited during |
| (press the Stop/reset key). Then | ||
will not |
| ||||
| Run Mode. |
| edit the parameter. | ||
change after |
|
| |||
|
|
|
| ||
an edit | True for all | • If you’re using the [SFT] intelligent | • Change the state of the SFT | ||
(reverts to old | parameters | input (software lock |
| input, and check the B031 | |
setting). |
| ||||
| [SFT] input ON? |
| parameter (SFT mode). | ||
|
|
| |||
|
|
|
|
|
Troubleshooting and Maintenance