B–4

Introduction

Serial Network

Parameter

Settings

Appendix B

Several parameter settings are necessary to configure serial communications, listed below.

Function

Item

Value

Description

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Digital operator

 

 

 

 

C070

Data command source

03

RS485 connector

 

 

04

Expansion card #1

 

 

 

 

 

 

 

 

05

Expansion card #2

 

 

 

 

 

 

02

Loop-back test

 

 

 

 

 

 

03

2400 bps

 

 

 

 

C071

Baud rate

04

4800 bps

 

 

 

 

 

 

05

9600 bps

 

 

 

 

 

 

06

19200 bps

 

 

 

 

 

 

1 to 32,

1 to 32 – Node or station address (unique

 

 

FF

to each inverter or device)

C072

Node address

 

FF – Automatic broadcast (to all nodes on

 

transmit, allowed only on certain

 

 

 

 

 

 

commands (refer to each command

 

 

 

description in this appendix)

 

 

 

 

C073

Data bits

07

7 bits

 

 

08

8 bits

 

 

 

 

 

 

 

 

00

none

 

 

 

 

C074

Parity

01

Even parity

 

 

 

 

 

 

02

Odd parity

 

 

 

 

C075

Stop bits

01

1 bit

 

 

02

2 bits

 

 

 

 

 

 

C078

Wait time

0 to 1000

0 to 1000 ms time that the inverter waits

 

 

 

to respond to network master

 

 

 

 

For inverters on the same network, some settings must match from inverter to inverter. These include:

Baud rate

Data bits

Parity

Stop bits

However, the node address on each inverter must be unique, used only once on the network.