3–54

“C” Group: Intelligent Terminal Functions

Configuring Drive

Parameters

 

 

 

 

 

“C” Function

 

Run

 

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

Units

 

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

 

 

Edit

 

–FE

–FU

 

–FR

 

 

 

Name

 

Description

 

 

 

 

 

 

 

 

 

Code

 

 

 

Lo Hi

 

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C031

Terminal [11] active

 

 

 

✘ ✔

 

00

00

 

00

 

 

>C031 OUT-TM

 

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-11

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C032

Terminal [12] active

 

 

 

✘ ✔

 

00

00

 

00

 

 

>C032 OUT-TM

 

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-12

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C033

Terminal [13] active

 

Select logic convention,

✘ ✔

 

00

00

 

00

 

 

>C033 OUT-TM

 

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-13

NO

 

 

 

 

 

two option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C034

Terminal [14] active

 

00 normally open N.O.

✘ ✔

 

00

00

 

00

 

 

>C034 OUT-TM

 

 

 

01 normally closed N.C.

 

 

 

 

 

 

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-14

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C035

Terminal [15] active

 

 

 

✘ ✔

 

00

00

 

00

 

 

>C035 OUT-TM

 

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-15

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C036

Alarm relay terminal

 

 

 

✘ ✔

 

01

01

 

01

 

 

>C036 OUT-TM

 

 

 

 

active state

 

 

 

 

 

 

 

 

 

 

 

 

 

O/C-AL

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Summary Table - This table shows all twenty-two functions for the logic output

 

 

 

 

 

terminals [11] – [15] at a glance. Detailed function descriptions, related parameters, settings,

 

 

 

and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4–42.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Function Summary Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

Terminal

 

Function Name

 

 

 

 

 

Description

 

 

 

 

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

RUN

 

Run signal

ON

 

Inverter is in Run Mode, motor running

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

Inverter is in Stop Mode, motor stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

FA1

 

Frequency arrival type

ON

 

when output to motor is at the standard set frequency

 

 

 

 

 

 

1 – constant speed

 

 

F001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

when output to motor is not at the set frequency F001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

FA2

 

Frequency arrival type

ON

 

when output to motor is at or above the FA

 

 

 

 

 

 

 

2 – over-frequency

 

 

Threshold 1 (C042) during accel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

when the output to motor is below the FA Threshold 1

 

 

 

 

 

 

 

 

 

 

(C043) during decel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

OL

 

Overload advance

ON

 

when output current is more than the set Threshold 1

 

 

 

 

 

 

notice signal (1)

 

 

for the overload signal (set with C041)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

when output current is less than the set

 

 

 

 

 

 

 

 

 

 

 

Threshold 1for the overload signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

OD

 

Output deviation for

ON

 

when PID error is more than the set threshold for the

 

 

 

 

 

 

PID control

 

 

deviation signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

when PID error is less than the set threshold for the

 

 

 

 

 

 

 

 

 

 

 

deviation signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

AL

 

Alarm signal

ON

 

when the alarm condition has been met and not reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

when the alarm had not tripped since the previous

 

 

 

 

 

 

 

 

 

 

 

power cycle or since the previous keypad reset