4–34

Using Intelligent Input Terminals

Operations and Monitoring

Force Operation from Digital Operator

This function permits a digital operator interface to override the Run command source setting (A002) when it is configured for a source other than the operator interface. When the [OPE] terminal is ON and the operator interface gives a Run command, the inverter uses the standard output frequency settings to operate the motor.

Opt.

 

Symbol

Function Name

Input

 

 

 

 

 

 

Description

 

 

 

Code

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

OPE

Force Operation

ON

Forces the operator interface Run

 

 

 

from Digital

 

command to over-ride commands from

 

 

 

Operator

 

input terminals (such as [FW], [RV]).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Run command operates normally, as

 

 

 

 

 

configured by A002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example: (Requires input configuration—

 

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

A001

 

 

see page 4–12.)

 

 

 

 

 

 

 

 

 

settings:

 

A002 (set not equal to 02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPE

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When changing the [OPE] state during Run

 

 

TH

FW

8

CM1

5

3

1

 

Mode (inverter is driving the motor), the

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

inverter will stop the motor before the new

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[OPE] state takes effect.

If the [OPE] input turns ON and the digital

operator gives a Run command while the inverter is already running, the inverter stops the motor. Then the digital operator can control the motor.

See I/O specs on page 4–9.