3–46

“B” Group: Fine-Tuning Functions

External Brake Control

The brake control function in the inverter controls external braking used in systems such as elevators. The purpose of this function is to ensure the inverter is powering the motor before releasing external brakes that would permit the load to move or coast. This function requires the configuration and wiring of intelligent input and output terminals. See “External Brake Control Function” on page 4–39 for more information.

 

 

 

 

“B” Function

Run

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

Units

SRW Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

 

 

 

 

Edit

–FE

–FU

 

–FR

 

 

 

 

Name

Description

 

 

 

 

 

 

 

 

 

Code

Lo Hi

(EU)

(US)

 

(JP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B120

Brake Control Enable

Two option codes:

✘ ✔

00

00

 

00

 

>b120 BRAKE

 

 

 

 

 

 

00 Disable

 

 

 

 

 

 

 

 

Mode

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B121

Brake Wait Time for

Sets time delay between

✘ ✔

0.00

0.00

 

0.00

 

sec.

>b121 BRAKE

 

 

 

 

 

Release

arrival at release frequency

 

 

 

 

 

 

 

 

STA-WAIT

0.00s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the brake release signal.

 

 

 

 

 

 

 

 

 

 

 

 

ConfiguringDrive

 

 

 

 

Range is 0.00 to 5.00 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

 

B122

Brake Wait Time for

Sets time delay after brake

✘ ✔

0.00

0.00

 

0.00

 

sec.

>b122 BRAKE

 

 

 

Acceleration

confirmation signal is

 

 

 

 

 

 

 

 

>b123 BRAKE

 

 

 

 

 

 

 

 

 

 

 

 

 

ACC-WAIT

0.00s

 

 

 

 

 

 

received until the inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

begins acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 5.00 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B123

Brake Wait Time for

Sets time delay after brake

✘ ✔

0.00

0.00

 

0.00

 

sec.

STP-WAIT

0.00s

 

 

 

 

 

Stopping

confirmation signal turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF until decelerating the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter to 0 Hz.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 5.00 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B124

Brake Wait Time for

Sets the wait time for confir-

✘ ✔

0.00

0.00

 

0.00

 

sec.

>b124 BRAKE

 

 

 

 

 

Confirmation

mation after turn ON/OFF of

 

 

 

 

 

 

 

 

BRK-WAIT

0.00s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

brake release. If confirma-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion is not received during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the specified wait time, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter will trip with an

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

external brake error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 5.00 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B125

Brake Release

Sets the frequency at which

✘ ✔

0.00

0.00

 

0.00

 

Hz

>b125 BRAKE

 

 

 

 

 

Frequency Setting

the inverter will output the

 

 

 

 

 

 

 

 

OPEN-F

000.00Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

brake release signal after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

delay set by B121.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 99.99 /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100.0 to 400.0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B126

Brake Release Current

Sets the minimum inverter

✘ ✔

Rated current for

A

>b126 BRAKE

 

 

 

 

 

Setting

current level above which

 

each inverter model

 

OPEN-A

00.16.5A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the brake release signal will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be permitted.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0% to 200% of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[BRK] Brake release

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

External Brake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[BOK] Brake confirmation

 

 

 

 

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[BER] Brake error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Brake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(or alarm, etc.)