1–10

SJ300 Inverter Specifications

Started

 

 

 

Item

General Specifications

 

 

 

 

 

 

 

 

 

 

 

Other user-settable parameters

V/F free-setting (up to 7 points), freq. upper/lower limit, freq. jump, accel/decel curve

 

 

 

 

 

 

 

selection, manual torque boost value and freq. adjustment, analog meter tuning, start

Geting

 

 

 

 

frequency, carrier frequency, electronic thermal protection level, external frequency

 

 

 

 

output zero/span reference, external frequency input bias start/end, analog input selec-

 

 

 

 

 

 

 

 

 

 

tion, retry after trip, restart after instantaneous power failure, various signal outputs,

 

 

 

 

 

reduced voltage start, overload restriction, default value setting (US, Europe, Japan),

 

 

 

 

 

deceleration and stop after power failure, AVR function, fuzzy accel/decel, auto-tuning

 

 

 

 

 

(on-line/off-line), high-torque multi-operation, automatic energy-saving operation

 

 

 

 

 

 

 

 

 

 

 

Carrier frequency range

Models SJ300–015xxx to 750xxx: 0.5 to 12 kHz

 

 

 

 

 

Models SJ300–900Hxx to 1320Hxx: 0.5 to 8 kHz

 

 

 

 

 

 

Protective functions

Over-current, overload, braking resistor overload, over voltage, EEPROM error, under-

 

 

 

 

 

voltage error, CT (current transformer) error, CPU error, external trip, USP error,

 

 

 

 

 

ground fault, input over voltage, instantaneous power failure, expansion card 1 error,

 

 

 

 

 

expansion card 2 error, inverter thermal trip, phase failure detection, IGBT error,

 

 

 

 

 

thermistor error

 

 

 

 

 

 

 

Environ-

 

Temperature (*9)

Operating (ambient): -10 to 50°C / Storage: -20 to 65°C

 

 

ment

 

 

 

 

 

 

Humidity

20 to 90% humidity (non-condensing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vibration *10

Models SJ300–004xxx to 220xxx: 5.9 m/s2 (0.6G), 10 to 55 Hz

 

 

 

 

 

Models SJ00–300xx to 1500xxx: 2.94 m/s2 (0.3G), 10 to 55 Hz

 

 

 

 

Location

Altitude 1,000 m or less, indoors (no corrosive gasses or dust)

 

 

 

 

 

 

 

 

Coating color

 

Gray

 

 

 

 

 

 

 

Accessories

 

Feedback PCB

SJ-FB (vector control loop speed sensor)

 

 

 

 

 

 

 

 

 

 

Digital input PCB

SJ-DG (4-digit BCD / 16-bit binary)

 

 

 

 

 

 

 

 

 

 

Others

EMI filters, input/output reactors, DC reactors, radio noise filters, braking resistors,

 

 

 

 

 

braking units, LCR filter, communication cables, factory I/O network interface cards

 

 

 

 

 

 

 

Operator input devices

OPE–SRE (4-digit LED with potentiometer) / OPE–S (4-digit LED w/o potentiometer),

 

 

 

 

 

Optional: OPE-SR (4-digit LED with potentiometer, Japanese/English overlay),

 

 

 

 

 

SRW–0EX Multilingual operator with copy function (English, French, German, Italian,

 

 

 

 

 

Spanish, and Portuguese)

 

 

 

 

 

 

Signal Ratings Detailed ratings are in “Specifications of Control and Logic Connections” on page 4–9.

 

Signal / ContactRatings

 

 

 

 

 

 

 

 

 

 

Built-in power for inputs

24VDC supply, 100 mA maximum

 

 

 

 

 

 

Intelligent (programmable) logic inputs

27VDC maximum, 4.7kΩ input impedance

 

 

 

 

 

 

Intelligent (programmable) logic outputs

Open collector type, 50mA max. ON state current, 27 VDC maximum OFF state voltage

 

 

 

 

 

 

Thermistor input

Minimum thermistor power 100mW

 

 

 

 

 

 

PWM output

0 to 10VDC, 1.2 mA max., 50% duty cycle

 

 

 

 

 

 

Voltage analog output

0 to 10VDC, 2 mA max.

 

 

 

 

 

 

Current analog output

4-20 mA, nominal load impedance 250Ω

 

 

 

 

 

 

Analog input, current

4 to 19.6 mA range, 20 mA nominal

 

 

 

 

 

 

Analog input, voltage

0 to 9.6 VDC range, 10VDC nominal, 12VDC max., input impedance 10 kΩ

 

 

 

 

 

 

+10V analog reference

10VDC nominal, 10 mA maximum

 

 

 

 

 

 

Alarm relay, normally closed contacts

Maximum loads: 250VAC, 2A; 30VDC, 8A resistive load

 

 

 

250VAC, 0.2A; 30VDC, 0.6A inductive load

 

 

 

Minimum loads: 100 VAC, 10mA; 5VDC, 100mA

 

 

 

 

 

 

Alarm relay, normally open contacts

250VAC, 1A; 30VDC 1A max. resistive load /

 

 

 

250VAC, 0.2A; 30VDC, 0.2A max. inductive load

 

 

 

Min. loads: 100 VAC, 10mA; 5VDC, 100mA