Using Intelligent Output Terminals

Operations and Monitoring

The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The inverter has several output functions that you can assign individually to five physical logic outputs. Along with these solid-state outputs, the alarm relay output has type Form C (normally open and normally closed) contacts. The relay is assigned the alarm function by default, but you can assign it to any of the functions that the open-collector outputs can use.

 

SJ300 inverter

Sinking outputs

 

Output circuits

(open collector)

common

CM2 15 14 13 12 11

L

L

L

L

L

External

system

– +

24VDC

TIP: The open-collector transistor outputs can handle up to 50mA each. We highly recommend that you use an external power source as shown. It must be capable of providing at least 250mA to drive the outputs at full load.

If you need output current greater than 50mA, use the inverter output to drive a small relay. Be sure to use a diode across the coil of the relay as shown (reverse- biased) in order to suppress the turn-off spike, or use a solid-state relay.

CM2

11

+

RY