4–15

SJ300 Inverter

The Bit Operation method of speed control uses up to seven intelligent inputs to select from up to eight speeds. Since the all-switches-OFF combination selects the first speed, you only need N-1 switches to select N speeds. With Bit Operation speed control, only one input is normally active at a time. If multiple switches are ON, the lower numbered input takes precedence (determines the speed). The table and figure below show how the input combinations work.

 

 

 

 

 

 

 

 

Speed

 

 

 

 

 

 

 

 

7th

Multi-

 

 

Input Function

 

 

6th

 

 

 

 

 

 

 

5th

speed

SF7

SF6

SF5

SF4

SF3

SF2

SF1

4th

 

 

 

 

 

 

 

 

 

3rd

 

 

 

 

 

 

 

 

Speed 0

0

0

0

0

0

0

0

2nd

 

 

 

 

 

 

 

 

Speed 1

1

1st

 

 

 

 

 

 

 

 

0th

Speed 2

1

0

 

 

 

 

 

 

 

 

 

 

Speed 3

1

0

0

Switches

 

 

 

 

 

 

 

 

SF1

Speed 4

1

0

0

0

 

 

 

 

 

 

 

 

 

SF2

Speed 5

1

0

0

0

0

 

 

 

 

 

 

 

 

 

SF3

Speed 6

1

0

0

0

0

0

 

 

 

 

 

 

 

 

SF4

Speed 7

1

0

0

0

0

0

0

 

 

 

 

 

 

 

 

SF5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SF6

SF7

Fwd Run

The following table lists the option codes for assigning [SF1 to [SF7] to the intelligent inputs.

Opt.

Symbol

Function Name

 

 

 

 

Description

 

 

 

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

 

SF1

Bit-level speed select 1

Bit-level speed select, Bit 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

 

SF2

Bit-level speed select 2

Bit-level speed select, Bit 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

 

SF3

Bit-level speed select 3

Bit-level speed select, Bit 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

SF4

Bit-level speed select 4

Bit-level speed select, Bit 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

SF5

Bit-level speed select 5

Bit-level speed select, Bit 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

37

 

SF6

Bit-level speed select 6

Bit-level speed select, Bit 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

 

SF7

Bit-level speed select 7

Bit-level speed select, Bit 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for

 

C001, C002, C003, C004,

Example: (Requires input configuration—

inputs:

 

 

C005, C006, C007, C008

see page 3–47. Jumper position shown is

 

 

 

 

for –xFU/-xFR models; for –xFE models,

Required

 

F001, A020 to A035

see page 4–12.)

 

SF7 SF5 SF3 SF1

settings:

 

A019=01

 

 

 

 

 

 

 

 

SF6 SF4 SF2

 

 

 

 

 

 

 

TH

FW

8

CM1

5

3

1

 

Notes:

 

 

 

 

 

 

 

P24

PLC

CM1

 

7

6

 

4

 

2

 

 

When all [SFx] inputs are OFF, the speed is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set by default to the value in F001.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When a multi-speed setting more than 50Hz(60Hz) is to be set, it is necessary to program the maximum frequency A004 high enough to allow that speed.

Operations Monitoring and