Configuring the Terminal Module
The
There are two jumpers for each channel; a P/J jumper and a V/I jumper.
The two jumpers work together.
Figure 1-13. P/J and V/I Jumpers
P/J Jumper The P/J jumper sets the channel output mode to be either Program Selectable or Jumper Selectable. When the jumper is in the program selectable position, the channel output mode can be set via programming commands. In the jumper selectable position, the channel output mode is set via the V/I jumper.
V/I Jumper The V/I jumper sets the channel output mode to either voltage or current when the P/J jumper is set to the Jumper Selectable position. When the P/J jumper is set to Program Selectable, this jumper has no effect.
Notes With no jumpers installed, the module will be in the Program Selectable output mode.
When the P/J Jumper is set to the Jumper Selectable position, the output mode cannot be changed with SCPI commands. The output mode following a *RST common command will be the mode set by the V/I jumper.
Chapter 1 | Module Setup and Installation 31 |