Lincoln Electric 200 service manual 56TROUBLESHOOTING & REPAIRF-56

Models: 200

1 145
Download 145 pages 41.63 Kb
Page 126
Image 126

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

F-56TROUBLESHOOTING & REPAIRF-56

MAIN GENERATOR FRAME REMOVAL AND REPLACEMENT PROCEDURE

(CONTINUED)

FIGURE F.23 – FRONT PANEL FASTENER REMOVAL

BOLTS / NUTS / WASHERS (2)

MIDDLE SCREW (1)

BASE MOUNTING BOLTS (4)

Return to Section TOC

Return to Master TOC

23.Using the 1/2” wrench, remove the two bolts, nuts, and washers that hold the front panel assembly to the horizontal rails. (There is one on each side.) See Figure F.23.

24.Using the 9/16” wrench, remove the four bolts, nuts, and washers from the bottom of the front panel assembly. These four bolts mount the front to the base. (There are two on each side.) See Figure F.23.

25.Using the 3/8” nut driver, remove the screw from the lower middle of the front panel. See Figure F.23.

26.Carefully remove the front panel assembly.

Return to Section TOC

Return to Master TOC

PIPELINER® 200

Page 126
Image 126
Lincoln Electric 200 service manual 56TROUBLESHOOTING & REPAIRF-56