8: Device Ports

 

 

 

 

 

 

 

 

 

 

should be on, off, or returned to the state it was in before the

 

 

reboot. Default is Off.

 

 

Last State

Select whether to return the outlet to the state it was in before

 

 

the reboot.

 

 

Reboot

To power cycle the outlet, select the checkbox. Default is

 

 

unchecked.

 

 

Note: You can reboot the SLB branch office manager on the

 

 

Maintenance page, but after the reboot, the power outlet has the

 

 

same power state as it did before the reboot.

4. To save, click Apply.

Power Outlet Commands

The following CLI commands correspond to the web page entries described above.

To configure and control power outlets:

set power switchingdelay <Delay in msec>

set power alarmthreshold <disableTenths of Amps>

set power outlet <Outlet # or List or Name> <one or more parameters>

Parameters:

name <Outlet Name>

description <Outlet Description> state <onoff>

wakeup <onofflaststate> reboot

Example: set power outlet 1-2,4 state on

To view power outlet settings:

show power [outlet <Outlet # or Name>]

Note: The screen displays PND when the outlet is powering up and is waiting for the delay period to expire. It displays RBT when an outlet has been told to reboot and is waiting for the reboot interval to expire (default is 20 seconds). The switching delay and the reboot interval are completely independent of each other.

Host Lists

A host list is a prioritized list of SSH, Telnet, and TCP hosts available for establishing incoming modem connections or for the connect direct command on the CLI. The SLB branch office manager cycles through the list until it successfully connects to one.

To add a host list:

1.Click the Devices tab and select the Host Lists option. The following page displays:

SLB™ Branch Office Manager User Guide

108

Page 108
Image 108
Lantronix 900-510 Host Lists, Power Outlet Commands, To configure and control power outlets, To view power outlet settings