Teledyne M300EM MODBUS Coil Registers, single-bit;read/write, Modbus, Description, Units, A-38

Models: M300E M300EM

1 398
Download 398 pages 30.02 Kb
Page 360
Image 360
APPENDIX A-7: MODBUS Register Map

 

APPENDIX A-7: MODBUS Register Map

Teledyne API - T300/T300M and M300E/EM PN 04906H (DCN5840)

 

 

 

 

 

 

 

 

MODBUS

 

Description

Units

 

 

Register Address

 

 

 

 

 

(dec., 0-based)

 

 

 

 

 

 

 

MODBUS Coil Registers

 

 

 

 

 

(single-bit; read/write)

 

 

0

1

2

3

204

214

224

234

1Optional

Maps to relay output signal 36 (MB_RELAY_36 in signal I/O list) Maps to relay output signal 37 (MB_RELAY_37 in signal I/O list) Maps to relay output signal 38 (MB_RELAY_38 in signal I/O list) Maps to relay output signal 39 (MB_RELAY_39 in signal I/O list) Triggers zero calibration of range #1 (on enters cal.; off exits cal.) Triggers span calibration of range #1 (on enters cal.; off exits cal.) Triggers zero calibration of range #2 (on enters cal.; off exits cal.) Triggers span calibration of range #2 (on enters cal.; off exits cal.)

2O2 option

3CO2 option

4Set DYN_ZERO or DYN_SPAN variables to ON to enable calculating new slope or offset. Otherwise a calibration check is performed.

A-38

04188D DCN5752

Page 360
Image 360
Teledyne M300EM MODBUS Coil Registers, single-bit;read/write, Modbus, Description, Units, Register Address, dec., 0-based