Teledyne M300EM operation manual Signal Name, Bit or Channel Number, Description, A-27

Models: M300E M300EM

1 398
Download 398 pages 30.02 Kb
Page 349
Image 349
A-27

Teledyne API - T300/T300M and M300E/EM PN 04906H (DCN5840)

APPENDIX A-4: Signal I/O Definitions

Signal Name

Bit or Channel

Number

Description

Alarm outputs, U21, J1009, pins 112 = bits 47, default I/O address 325 hex

ST_SYSTEM_OK2

4

1

= system OK

 

 

0

= any alarm condition or in diagnostics mode

 

 

 

 

ST_CONC_ALARM_1 8

5

1

= conc. limit 1 exceeded

 

 

0

= conc. OK

ST_HIGH_RANGE 10 + 13

5

1

= high auto-range in use

 

 

0

= low auto-range

ST_CONC_ALARM_2 8

6

1

= conc. limit 2 exceeded

 

 

0

= conc. OK

 

 

 

 

ST_ZERO_CAL 10 + 13

6

1

= in zero calibration

 

 

0

= not in zero

 

 

 

 

ST_HIGH_RANGE2 16

7

1

= high auto-range in use (mirrors ST_HIGH_RANGE

 

 

status output)

 

 

0

= low auto-range

A status outputs, U24, J1017, pins 18 = bits 07, default I/O address 323 hex

ST_SYSTEM_OK

0

0

= system OK

 

 

1

= any alarm condition

ST_CONC_VALID

1

0

= conc. valid

 

 

1

= hold off or other conditions

 

 

 

ST_HIGH_RANGE

2

0 = high auto-range in use

 

 

1

= low auto-range

 

 

 

 

ST_ZERO_CAL

3

0

= in zero calibration

 

 

1

= not in zero

ST_SPAN_CAL

4

0

= in span calibration

 

 

1

= not in span

ST_DIAG_MODE

5

0

= in diagnostic mode

 

 

1

= not in diagnostic mode

ST_AUTO_REF 3

6

0

= in auto-reference mode

 

 

1

= not in auto-reference mode

 

7

Spare

B status outputs, U27, J1018, pins 18 = bits 07, default I/O address 324 hex

ST_AUTO_REF 2

0

0

= in auto-reference mode

 

 

1

= not in auto-reference mode

 

1–5

Spare

 

 

 

 

ST_CO2_CAL 7

6

0

= in CO2 calibration

 

 

1

= not in CO2 calibration

ST_O2_CAL 5

7

0

= in O2 calibration

 

 

1

= not in O2 calibration

A-27

Page 349
Image 349
Teledyne M300EM operation manual Signal Name, Bit or Channel Number, Description, A-27