Fiber Testing 4
Calibrating the Tester
Agilent FrameScope350 User’s Manual 97
5On the Fiber Main Menu, press Calibration. The Fiber Calibration
screen displays.
6Choose Double Ended, and press Next. The Fiber Detection screen
displays.
7When the message below the diagram reads, “Ready to Calibrate,”
press OK. The Calibration window opens.
8When the window reads, “Calibration Successful,” press OK in the
window. The Fiber Main Menu displays. Remove the cou plers and
use the coupler ends of the jumpers when changing connections.
Leave the cable connections to the FiberProbes intact
Method B

Method B or the 1-jumper method is usually recommended for

multimode fiber.